![Immergas AVIO 24 2 ERP Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/immergas/avio-24-2-erp/avio-24-2-erp_instruction-booklet-and-warning_2047755009.webp)
9
1-8
1-9
V4
V2
V3
A4
A3
A2
INS
TALL
AT
O
R
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
Circulating pump LED
(first red LED)
Description
Diagnostics
Remedy
R Y
Y
Y
Y
On Off Off Off On
Circulator pump blocked
The circulator pump cannot restart
automatically due to an anomaly
Wait for the circulator to make auto-
matic release attempts or manually
release the motor shaft acting on the
screw in the centre of the head.
If the anomaly persists replace the
circulator.
R Y
Y
Y
Y
On Off Off On Off
Abnormal situation (the circulator
continues operating).
low power supply voltage
Voltage off range
Check power supply
R Y
Y
Y
Y
On Off On Off Off
Electrical fault
(Circulator pump blocked)
The circulator is locked due to power
supply too low or serious malfunction
Check the power supply, if the anomaly
persists replace the circulator
Total head available to the plant.
Key:
V2 = Total head available to the system with
pump at speed 2
V3 = Total head available to the system with
pump at speed 3
V4 = Total head available to the system with
pump at speed 4
A2 = Power absorbed by the pump at speed 2
A3 = Power absorbed by the pump at speed 3
A4 = Power absorbed by the pump at speed 4
Ci
rcu
la
to
r p
um
p a
bs
or
be
d p
ow
er (
W
)
Capacity (l/h)
To
ta
l h
ea
d (kP
a)
1.18 KITS AVAILABLE ON REQUEST.
• Kit of system shutoff valves (on request). The
boiler is designed for installation of system
shutoff valves to be placed on delivery and
return pipes of the connection assembly. This
kit is particularly useful for maintenance as
it allows the boiler to be drained separately
without having to empty the entire system.
• System zone Kit (on request). If the heating
system is to be divided into several zones (
max.
three
), in order to interlock them with separate
adjustments and to keep water flow rate high
for each zone, Immergas supplies zone system
kits by request.
• Polyphosphate batching kit (on request). The
polyphosphate dispenser Reduces the forma-
tion of lime-scale and preserves the original
heat exchange and domestic hot production
water conditions. The boiler is prepared for
application of the polyphosphate dispenser kit.
The above kits are supplied complete with in-
structions for assembly and use.