2.5  IGNITION OF THE BOILER.

Before ignition make sure the heating system is 

filled with water and that the manometer (12) 

indicates a pressure of 1÷1,2 bar.

- Open the gas cock upstream from the boiler.
- Turn the master switch (9) taking it to 

the Domestic/Remote Friend Control

V2

 

(CAR

V2

) (

)or Domestic Hot Water  

(

)position.

N.B.: 

Once the main selector switch has been 

placed (9) on one of these positions, the presence 

of voltage is indicated by the switch-on with a 

fixed light of one of the LEDS from 4 to 8, which 

indicate the temperature of the output water from 

the main heat exchanger

.

Important: 

flashing of one of the LEDs from 4 

to 8 indicates that there is an anomaly present, 

refer to the successive paragraph.
Functioning of the boiler in domestic water mode 

and in heating mode is indicated respectively by 

the switch-on of LED 2 or LED 3 with a fixed light 

(in absence of remote controls).
• Operation with Remote Friend Control

V2

 

(Optional). With selector switch (9) in position 

(

) and Remote Control connected to 

the boiler selector switches (10) and (11) 

excluded. The boiler adjustment parameters 

are set from the control panel of the Remote 

Friend Control

V2

. Connection to the Remote 

Control is indicated by the contemporary fixed 

switch-on of LEDs 2 and 3 (

). Also in the 

presence of Remote Control the indications of 

the temperature and any faults are maintained 

on the control panel.

• 

Operation without Remote Control. With the 

selector switch (9) in position (

) the 

heating adjustment selector switch is cut out, 

the domestic hot water temperature is regulated 

by selector switch (10). With the selector switch 

in position (

)the heating adjustment 

selector switch (11) is used to regulate the 

temperature of radiators, while selector (10) 

continues to be used for domestic hot water. 

Turn the selector switches in a clockwise 

direction to increase the temperature and in 

an anti-clockwise direction to decrease it.

From this moment the boiler functions 

automatically. With no demand for heat (heating 

or domestic hot water production) the boiler 

goes to “standby” function, equivalent to the 

boiler being powered without presence of 

flame (LED corresponding to the ignited boiler 

temperature). Each time the boiler lights up, the 

relative flame present symbol is displayed by the 

green LED 1 ( ).

N.B.:

 the boiler may start-up automatically if the 

anti-freeze function is activated.

2.6  FAULT AND ANOMALY SIGNALS.

The Avio 24 2 ERP boiler signals ant anomaly by 

flashing of one of the LEDs from 4 to 8 or LEDs 1 

and 2 coupled to LED 7. On any remote controls, 

the error code will be displayed using a numerical 

code preceeded or followed by the letter E (e.g. 

CAR

V2

 = Exx, Mini CRD = xxE).

Flashing LED Error 

Code

Anomaly signalled

Cause

Boiler status / Solution

Led 6 ( )

01

No ignition block

In the event of request of room central heating or domes-

tic hot water production, the boiler does not switch on 

within the preset time. If this does not occur within 10 

seconds, the boiler remains in stand-by for 30 seconds, try 

again and if the second attempt fails it goes into “ignition 

block” (flashing LED 6).

To eliminate “no ignition block” the 

main switch (9) must be temporarily 

turned to the Reset position (1).

Warning:

 the fault may be reset up 

to 5 times consecutively, after which 

the function in inhibited for at least 

one hour. One attempt is gained every 

hour for a maximum of 5 attempts. By 

switching the appliance on and off the 

5 attempts are re-acquired.

On commissioning or after extended in-

activity it may be necessary to eliminate 

the “no ignition block”.

Led 7 ( )

02

Safety thermostat 

block (over-temper-

ature)

During operation, if a fault causes excessive overheating 

internally, in the exhaust, or an anomaly occurs in the flame 

control section, an overheating block is triggered in the 

boiler (LED 7 flashing).

To eliminate the “overheating block” the 

main switch (9) must be temporarily 

turned to the Reset position (1).

Led 8 ( )

03

Flue safety thermo-

stat block

The fume evacuation pipe does not function correctly 

(code 03).

The boiler goes into stand-by for 30 

minutes, after which, if normal work-

ing conditions are restored, it re-starts 

without having to be reset. In the case 

of 3 consecutive blocks, the boiler itself 

blocks and it must be reset in order to 

re-start (1).

Led 2 ( ) 

 and 7 ( ) 

blinking 

at the same time

04

Contacts resistance 

block

This occurs in the case of faults to the safety thermostat 

over-temperature).

The boiler does not start (1).

Led 5 ( )

05

Flow probe 

anomaly

The board detects an anomaly on the flow probe.

The boiler does not start (1).

Led 2 ( )

12

Storage tank probe 

anomaly

If the board detects a fault on the storage tank probe.

The boiler does not start in domestic 

hot water mode however, it remains in 

heating mode (1).

(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Technical After-Sales Service).

(2) Error codes over 31 are not shown on the CAR

V2

 display.

Содержание AVIO 24 2 ERP

Страница 1: ...tenance Technician IE 1 038455ENG Wall hung boiler with storage tank open chamber type B and natural draught The European regulation 813 2013 provides that this boiler can be installed only to replace...

Страница 2: ...the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by t...

Страница 3: ...s 13 2 7 Boiler shutdown 14 2 8 Restoring heating system pressure 14 2 9 Draining the system 14 2 10 Draining the boiler 14 2 11 Anti freeze protection 14 2 12 Case cleaning 14 2 13 Decomissioning 14...

Страница 4: ...leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household appliances For the aforementioned reasons we recommend not placi...

Страница 5: ...nger it is recommended to install the polyphosphate proportioner kit in the presence of water whose characteristics can give rise to scale deposits 1 7 ELECTRICAL CONNECTION The Avio 24 2 ErP boiler h...

Страница 6: ...nnot be used for plants divided into zones Electrical connection of the Remote Friend ControlV2 chronothermostat On Off Op tional or Mini The operations described below must be performed after having...

Страница 7: ...eck if the cap is loose Open the radiator air vent valves Close vent valves only when water is delivered Close the filling valve when the boiler pressure gauge indicates approx 1 2 bar N B During thes...

Страница 8: ...fficient to press button 1 once To change operation mode press the button for between 2 to 10 seconds until the current configuration flashing each time the button is pressed all possible functions ar...

Страница 9: ...tal head available to the system with pump at speed 4 A2 Power absorbed by the pump at speed 2 A3 Power absorbed by the pump at speed 3 A4 Power absorbed by the pump at speed 4 Circulator pump absorbe...

Страница 10: ...motorised 7 System filler tap 8 System expansion tank 9 Domestic water probe 10 Stainless steel boiler 11 3 bar safety valve 1 19 BOILER COMPONENTS 12 System emptying tap 13 8 bar safety valve 14 Boi...

Страница 11: ...d dangerous to obstruct the air intake even partially for the ventilation of the room in which the boiler is installed Due to the danger operation is also prohibited in the same room as suction device...

Страница 12: ...anti freeze function is activated 2 6 FAULT AND ANOMALY SIGNALS The Avio 24 2 ERP boiler signals ant anomaly by flashing of one of the LEDs from 4 to 8 or LEDs 1 and 2 coupled to LED 7 On any remote...

Страница 13: ...tioned on Summer or Winter To avoid keeping the system switched on in case of a prolonged absence the system must be drained completely or antifreeze substances added to the heating system water In bo...

Страница 14: ...e appliance combustion products check that there is no backflow of combustion products into the room even during functioning of fans 3 1 HYDRAULIC LAYOUT Key 1 Gas valve 2 Stainless steel coil for boi...

Страница 15: ...out by an authorised company e g Authorised After Sales Technical Assistance Service Smell of gas Caused by leakage from gas circuit pipelines Check sealing efficiency of gas intake circuit Irregular...

Страница 16: ...ases and in an anti clockwise direction it decreases Adjust the boiler minimum thermal input Fig 3 3 N B only proceed after having calibrated the nominal pressure Adjustment of the minimum thermal inp...

Страница 17: ...ng Led 8 Heating switch on delay request from Room thermostat and Remote Friend ControlV2 The boiler is set to switch on immediately after a request In the case of particular plants e g area plants wi...

Страница 18: ...ntion of electrical main electrical switch on boiler system control thermostat intervention domestic water control thermostat intervention Check that the internal system is properly sealed according t...

Страница 19: ...at 0 of O2 at Q Nom Min ppm 177 81 279 115 240 108 Flue temperature at nominal heat output C 101 106 104 Flue temperature at minimum heat output C 74 77 76 METHANE G20 BUTANE G30 PROPANE G31 HEAT POW...

Страница 20: ...2 40 0 57 Heat loss at flue with burner On Off 7 20 0 43 Heating circuit max working pressure bar 3 Heating circuit max working temperature C 90 Adjustable heating temperature C 35 85 Total volume sys...

Страница 21: ...e technical data are shown on the boiler data plate ENG Model Model code Serial Number Check PIN code Type of installation ref CEN TR 1749 Minimum heating capacity domestic Minimum heating capacity he...

Страница 22: ...partial load elmin 0 014 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 003 kW Emissions of nitrogen oxides NOX 132 mg kWh For mixed central heating appliances Stated load p...

Страница 23: ...ntary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C From...

Страница 24: ...energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further facto...

Страница 25: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Страница 26: ...under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3...

Страница 27: ......

Страница 28: ...mergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038455ENG rev ST 002233 003 04 18 Irlandese...

Отзывы: