parameter selected. The value is indicated by the 

slow flashing of one of the LEDs between 1 and 

8. The value is selected by rotating the heating 

temperature selector switch (11).

Once the value of the parameter to be modified 

has been selected, confirm the selection by 

momentarily turning the main selector switch 

onto Reset momentarily until the LED relative to 

the parameter switches off, then release.

Programming mode is exited if no operation is 

carried out for 30 seconds or if the main selector 

switch is positioned at OFF from the “parameter 

setting” level.

For association of the LED to the relative value, 

see the following tables:

Heating power.

 The boiler is produced and 

calibrated in the heating phase at nominal power. 

It also has electronic modulation that adapts 

the boiler potentiality to the effective heating 

demand of the house. Then the boiler works 

normally in a variable gas pressure field between 

the minimum heating power and the maximum 

heating power depending on the plants heating.

N.B:

 the selection of the “Minimum heating 

power” and “Maximum heating power” 

parameters, in the presence of a heating demand 

, allows switch-on of the boiler and power supply 

of the modulator with current equal to the value 

of the respective selected parameter.

Minimum heating power 

(continuous variation)

Flash-

ing LED 

(slow)

0% Imax. (Standard setting)

Led 1

7% Imax.

Led 2

14% Imax.

Led 3

21% Imax.

Led 4

28% Imax.

Led 5

35% Imax.

Led 6

42% Imax.

Led 7

63% Imax.

Led 8

Maximum heating power 

(continuous variation)

Flash-

ing LED 

(slow)

0% Imax.

Led 1

11% Imax.

Led 2

22% Imax.

Led 3

33% Imax.

Led 4

44% Imax.

Led 5

55% Imax.

Led 6

88% Imax.

Led 7

100% Imx. (Standard setting)

Led 8

Permanent reduction of the timer.

 The boiler 

has an electronic timing device that prevents the 

burner from igniting too often in the heating 

phase. The boiler has a standard supply of a timer 

adjusted at 180 seconds.

Heating switch-on timer 

(continuous variation)

Flash-

ing LED 

(slow)

30 seconds

Led 1

55 seconds

Led 2

80 seconds

Led 3

105 seconds

Led 4

130 seconds

Led 5

155 seconds

Led 6

180 seconds (Standard setting)

Led 7

255 seconds

Led 8

Heating ramp timing.

 The boiler distributes he 

maximum power set in the previous parameter. 

The boiler performs an ignition ramp of about 

650 seconds to arrive from minimum power to 

nominal heating power.

Heating ramp timer (continu-

ous variation)

Flash-

ing LED 

(slow)

65 seconds

Led 1

130 seconds

Led 2

195 seconds

Led 3

390 seconds

Led 4

455 seconds

Led 5

520 seconds

Led 6

585 seconds

Led 7

650 seconds (Standard setting)

Led 8

Heating switch-on delay request from Room 

thermostat and Remote Friend Control

V2

.

 The 

boiler is set to switch-on immediately after a 

request. In the case of particular plants (e.g. area 

plants with motorised thermostatic valves etc.) it 

could be necessary to delay switch-on.

Heating switch-on delay re-

quest from Room thermostat 

and Remote Friend Control

V2

 

(continuous variation).

Flash-

ing LED 

(slow)

0 seconds (Standard setting)

Led 1

54 seconds

Led 2

131 seconds

Led 3

180 seconds

Led 4

206 seconds

Led 5

355 seconds

Led 6

400 seconds

Led 7

510 seconds

Led 8

Domestic water thermostat/Boiler hysterisis.

 

With the setting of hysteresis 1 the boiler switches 

on with a boiling device temperature equal to a 

set point at -3°C. With the setting of hysteresis 

2 the boiler switches on with a boiling device 

temperature equal to a set point at -10°C.

Domestic water thermostat/

Boiler hysterisis

Flash-

ing LED 

(slow)

Hysteresis 1 (Standard setting)

Led 1

Hysteresis 1 

Led 8

Circulating pump function.

 Two circulating 

pump operational modes

can be selected in heating phase.

In “intermittent” mode it is activated from the 

environmental thermostat or from the remote 

control, in “continual” mode the circulation 

pump functions constantly when the main selec-

tor switch (12) is on heating mode.

Circulating pump function

Flash-

ing LED 

(slow)

Intermittent (Standard setting)

Led 1

Continuous

Led 8

Town Gas G110 - Industrial gas.

 The setting 

of this function is used to ad just the boiler in 

order to function with gases from the first family.

Town Gas G110 - Industrial 

gas (first family gas)

Flash-

ing LED 

(slow)

Off (Standard setting)

Led 1

On

Led 8

Boiler mode.

 Establishes if the boiler functions 

in instantaneous mode or with boiler (standard 

supply).

Boiler mode

Flash-

ing LED 

(slow)

Instantaneous (Cannot be 

used)

Led 1

With boiler (Standard setting)

Led 8

3.8  AUTOMATIC SLOW IGNITION 

FUNCTION WITH TIMED RAMP 

DELIVERY.

In the switch-on phase the electronic card car-

ries out an increasing gas delivery ramp (with 

pressure values that depend on the type of gas 

selected) of preset duration. This avoids every 

boiler lighting phase calibration or preparation 

operation in any conditions of use.

3.9  “CHIMNEY SWEEP” FUNCTION.

When activated, this function forces the boiler 

at max. output for 15 minutes.

IIn this mode all the adjustments are cut out and 

only the temperature safety thermostat and the 

limit thermostat remain active. To activate the 

“Chimney-Sweep” function, press the Reset key 

for 8 to 15 seconds in absence of domestic water 

and heating requests. Its activation is indicated 

by the simultaneous flashing of LEDS (2) and 

(3).This function allows the technician to check 

the combustion parameters. After the checks 

deactivate the function, switching the boiler off 

and then on again.

Содержание AVIO 24 2 ERP

Страница 1: ...tenance Technician IE 1 038455ENG Wall hung boiler with storage tank open chamber type B and natural draught The European regulation 813 2013 provides that this boiler can be installed only to replace...

Страница 2: ...the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by t...

Страница 3: ...s 13 2 7 Boiler shutdown 14 2 8 Restoring heating system pressure 14 2 9 Draining the system 14 2 10 Draining the boiler 14 2 11 Anti freeze protection 14 2 12 Case cleaning 14 2 13 Decomissioning 14...

Страница 4: ...leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household appliances For the aforementioned reasons we recommend not placi...

Страница 5: ...nger it is recommended to install the polyphosphate proportioner kit in the presence of water whose characteristics can give rise to scale deposits 1 7 ELECTRICAL CONNECTION The Avio 24 2 ErP boiler h...

Страница 6: ...nnot be used for plants divided into zones Electrical connection of the Remote Friend ControlV2 chronothermostat On Off Op tional or Mini The operations described below must be performed after having...

Страница 7: ...eck if the cap is loose Open the radiator air vent valves Close vent valves only when water is delivered Close the filling valve when the boiler pressure gauge indicates approx 1 2 bar N B During thes...

Страница 8: ...fficient to press button 1 once To change operation mode press the button for between 2 to 10 seconds until the current configuration flashing each time the button is pressed all possible functions ar...

Страница 9: ...tal head available to the system with pump at speed 4 A2 Power absorbed by the pump at speed 2 A3 Power absorbed by the pump at speed 3 A4 Power absorbed by the pump at speed 4 Circulator pump absorbe...

Страница 10: ...motorised 7 System filler tap 8 System expansion tank 9 Domestic water probe 10 Stainless steel boiler 11 3 bar safety valve 1 19 BOILER COMPONENTS 12 System emptying tap 13 8 bar safety valve 14 Boi...

Страница 11: ...d dangerous to obstruct the air intake even partially for the ventilation of the room in which the boiler is installed Due to the danger operation is also prohibited in the same room as suction device...

Страница 12: ...anti freeze function is activated 2 6 FAULT AND ANOMALY SIGNALS The Avio 24 2 ERP boiler signals ant anomaly by flashing of one of the LEDs from 4 to 8 or LEDs 1 and 2 coupled to LED 7 On any remote...

Страница 13: ...tioned on Summer or Winter To avoid keeping the system switched on in case of a prolonged absence the system must be drained completely or antifreeze substances added to the heating system water In bo...

Страница 14: ...e appliance combustion products check that there is no backflow of combustion products into the room even during functioning of fans 3 1 HYDRAULIC LAYOUT Key 1 Gas valve 2 Stainless steel coil for boi...

Страница 15: ...out by an authorised company e g Authorised After Sales Technical Assistance Service Smell of gas Caused by leakage from gas circuit pipelines Check sealing efficiency of gas intake circuit Irregular...

Страница 16: ...ases and in an anti clockwise direction it decreases Adjust the boiler minimum thermal input Fig 3 3 N B only proceed after having calibrated the nominal pressure Adjustment of the minimum thermal inp...

Страница 17: ...ng Led 8 Heating switch on delay request from Room thermostat and Remote Friend ControlV2 The boiler is set to switch on immediately after a request In the case of particular plants e g area plants wi...

Страница 18: ...ntion of electrical main electrical switch on boiler system control thermostat intervention domestic water control thermostat intervention Check that the internal system is properly sealed according t...

Страница 19: ...at 0 of O2 at Q Nom Min ppm 177 81 279 115 240 108 Flue temperature at nominal heat output C 101 106 104 Flue temperature at minimum heat output C 74 77 76 METHANE G20 BUTANE G30 PROPANE G31 HEAT POW...

Страница 20: ...2 40 0 57 Heat loss at flue with burner On Off 7 20 0 43 Heating circuit max working pressure bar 3 Heating circuit max working temperature C 90 Adjustable heating temperature C 35 85 Total volume sys...

Страница 21: ...e technical data are shown on the boiler data plate ENG Model Model code Serial Number Check PIN code Type of installation ref CEN TR 1749 Minimum heating capacity domestic Minimum heating capacity he...

Страница 22: ...partial load elmin 0 014 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 003 kW Emissions of nitrogen oxides NOX 132 mg kWh For mixed central heating appliances Stated load p...

Страница 23: ...ntary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C From...

Страница 24: ...energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further facto...

Страница 25: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Страница 26: ...under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3...

Страница 27: ......

Страница 28: ...mergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038455ENG rev ST 002233 003 04 18 Irlandese...

Отзывы: