Heating / cooling system configuration menu “
ConF
”
Menu item
Description
Adjustment range
Default
value
i201
System type selection for zone 1
0 = heating only
1 = heating / cooling
2 = heating / cooling with dehumidi-
fier with calculation of the dew point
3 = cooling only
4 = cooling only and dehumidifier
with calculation of the dew point
0
i202
System type selection for zone 2
1
i203
System type selection for zone 3
1
MPdC
Heat pump model
Allows to choose the model of the heat pump to be combined
with the boiler. In the event value 0 is selected, the commu-
nication anomaly with the heat pump is inhibited and all the
requests are sent directly to the boiler.
0 = no heat pump
1 = Audax 6kW
2 = Audax 8 kW
3 = Audax 10 kW
4 = Audax Top 6 kW
5 = Audax Top 8 kW
6 = Audax Top 12 kW
0
PEE1
Electricity price
Allows to enter the price of electricity in € cents per kWh for
time slot 1
19.10
h1on
Start of time slot 1 Allows to set when time slot 1 starts (hours)
8
M1on
Start of time slot 1 Allows to set when time slot 1 starts (minutes)
00
h1of
End of time slot 1 Allows to set when time slot 1 ends (hours)
19
M1of
End of time slot 1 Allows to set when time slot 1 ends (minutes)
00
PEE2
Electricity price
Allows to enter the price of electricity in € cents per kWh for
time slot 2
18.10
h2on
Start of time slot 2 Allows to set when time slot 2 starts (hours)
19
M2on
Start of time slot 2 Allows to set when time slot 2 starts (minutes)
00
h2of
End of time slot 2 Allows to set when time slot 2 ends (hours)
08
M2of
End of time slot 2 Allows to set when time slot 2 ends (minutes)
00
PEE3
Electricity price
Allows to enter the price of electricity in € cents per kWh for
time slot 3
18.10
h3on
Start of time slot 3 Allows to set when time slot 3 starts (hours)
19
M3on
Start of time slot 3 Allows to set when time slot 3 starts (minutes)
00
h3of
End of time slot 3 Allows to set when time slot 3 ends (hours)
08
M3of
End of time slot 3 Allows to set when time slot 3 ends (minutes)
00
PGAS
Gas price
Allows to set the price of gas per m
3
88.90
tMAS
Integration time
Allows to set the maximum stand-by time for integration
(minutes)
0 ÷ 999
60
tbiu
Bivalent tempera-
ture
Allows to set the bivalent temperature or the calculation of the
COP for the use of the heat pump
0 = COP calculation
1 = use of the minimum temperature
for commutation
0
tmin
External commuta-
tion temperature
Allows to set the minimum external temperature for switching
from the heat pump to the boiler
-15 - 10 °C
0
def
Default
Allows to reset all default value parameters
ESC
Output
exit menu
-