12
Electronic Pressure Sensor 34D
Operation manual
7503756000000050 05/2019
8.2 Explanation of the menu
8.2.1 Explanation of the menu level 1
SPx/rPx
Upper / lower limit value for system pressure at which OUT1
switches with hysteresis setting. SP1/rP1 is displayed if the
parameter [Hno] or [Hnc] for OUT1 was set in the extended
functions "EF" menu.
FHx/FLx
Upper / lower limit value for system pressure at which OUT1
switches with window setting. FH1/FL1 appears when the
parameter [Fno] or [Fnc] was set for OUT1 in the menu
Extended Functions "EF".
EF
Extended functions / opening of menu level 2.
8.2.2 Explanation of the menu level 2
rES
Restore factory setting.
ou1
Output function for OUT1:
• Switching signal for the pressure limit values: hysteresis
function [H ..] or window function [F ..], either normally open [.
no] or normally closed [. nc].
ou2
Output function for OUT2:
Analogue signal for the current system pressure: 4...20 mA [I] or
0...10 V [U]
dS1 / dS2
Switch-on delay for OUT1.
dr1 / dr2
Switch-off delay for OUT1
uni
Standard unit of measurement for system pressure (display):
[bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [inHG] .
P-n
Output logic: pnp / npn.
Lo
Minimum value memory for system pressure.
Hi
Maximum value memory for system pressure.
dAP
Damping of the measured signal.
coLr
Assignment of the display colours "red" and "green" within the
measuring range.
cFL / cFH
Lower / upper value for colour change.
Parameter only active after selection of a freely definable colour
window in the coLr parameter: [r-cF] or [G-cF
diS
Update rate and orientation of the display.