L N E
PSU SET
T
O 230V
AC
Tocsin 700 Panel Overview
2 x 16 LCD Display
24V DC Panel Power
Digital Inputs
Jog Wheel
3 off Configurable
Relay Outputs
With Activation
Indication Lamps
Sounder/Flasher
Outputs
Fault Relay Outputs
RS 485 Detector
Data Highway
Connector Port 1
‘C1’
(Addressable Versions)
RS 485 Detector
Data Highway
Connector Port 2 ‘C2’
(Addressable Versions)
8 off 4-20mA Loop Inputs
Mains/DC Input
(Check Supply Option Before Use)
Grounding Points
RS232 Comm
Port
Backup Battery
Battery Connector
Power to Main PCB
24V PSU Input
Volt Free Contact Opens On Loss of Mains Power
Label Indicates
Voltage Input as
Shipped From Factory
By Default 230V AC
Use Switch to Change
if Necessary
Page 5 of 52
IMPORTANT
When first powering systems which include an IGD battery backup the batteries MUST be connected first for
correct operation. During initial startup the panel software will check the battery condition, if mains power is
applied first then the batteries cannot be functionally checked and the panel will report an error.
Control panels are usually shipped pre-configured with a basic alarm strategy. Before installation check the
documentation provided to ensure the programmed cause and effect matches the site requirement. If it does
not then the system will need to be re-programmed by the installer using the embedded panel software or
PC based T700 setup software.