FIND ADD SENSORS
FIND ADD SENSORS
EDIT LOW ADD 4100
EDIT LOW HIGH 4100
The FIND Command
If addressable gas detectors are cabled to either port 1 or 2 of the control panel then the FIND
command can be used to automatically install these detectors onto the panel. Note this option is usually
only run the first time detectors are connected and will already have been run if factory configuration
has been requested and undertaken. Running the FIND command again will overwrite any previously
stored information. This will include any alarm level set up as a newly installed detector will have default
alarm levels set automatically as part of the FIND function.
1
2
3
Select the FIND ADD SENSORS menu item
and the following setup screen is displayed.
Use the jog wheel to enter the first address in
the sequence you expect to find (usually
4100)
Note the low address number will be flashing.
Once correctly set press the jog wheel to
move to the next setting.
Now use the jog wheel to enter the highest
address you expect to find. Once set press
the jog wheel.
FINDING 4105
FOUND 2 SENSORS
The system now checks through each
possible address in the range selected and
tries to communicate to each address in turn.
The top line of the display indicates the
current address being searched for and the
bottom line of the display shows the total
number of detectors found so far
Page 36 of 52