LCD CONTRAST
WARMUP MINS
T90 (Secs)
FAULT THRESHOLD
ALARM THRESHOLD
MUTE MESSAGE
MUTE TIME
MODBUS ADDRESS
MODBUS BAUD RATE
MODBUS DATA BITS
MODBUS PARITY
MODBUS STOP BITS
CUSTOM GAS
CUSTOM UNITS1
CUSTOM UNITS2
RESET TO DEFAULTS
REPROGRAM
CUSTOM GAS2
CUSTOM GAS3
CUSTOM GAS4
CUSTOM GAS1
EXIT
1
Set Display Brightness (1 to 10)
Set The Number of Minutes The panel is in Warm up Mode For (2 to 240)
Set the 4-20mA input Filter Level (0 to 100 Secs to T90)
Reset the control panel to its default values and settings.
Select this option when updating the Tocsin 700 firmware using the
Tocsin 700 PC Set up software. Note connect to the control panel
first then enter factory settings mode and select REPROGRAM.
Select to add a custom gas type to the selectable list of
gases. Input and store any 4 digit reference and it is added
to the list of gas types that can be selected (i.e FLAM, CO etc)
Select to add a custom UNIT to the selectable list of
UNITS (for example PPM, %VOL etc. Input and store any 3 digit reference
and it is added to the list of unit types that can be selected
Set the Level for Fault Detection on the Addressable Comm’s Ports
(8 to 99 consecutive errors communicating to a sensor before
reporting a system fault)
Set the number of seconds the gas level must exceed the set
alarm level for before setting the alarm relay.
Display ‘PRESS TO MUTE ALARM’ message on bottom line of display
when an alarm is active (ENABLE or DISABLE option). If disabled then
channel tag is displayed.
Set the time period for which an alarm will stay muted before
returning to its alarm condition
Set the Modbus address default is 100
Set the Modbus baud rate default is 19200
Set the Modbus data bits default is 8 bits
Set the Modbus parity default is none
Set the Modbus stop bits default is 1
Menu Overview Production Menu
WARNING
DO NOT ALTER THESE SETTINGS WITHOUT TRAINING OR
GUIDANCE FROM OLIVER IGD. IMPROPER SETTING OF
THESE PARAMETERS MAY RESULT IN UNINTENDED
OPERATION