PCB DIP Switch Selection.
4
3
2
1
On Off
DIP switch 1
is used to set battery size, set to OFF for
1.2Ah batteries. Set to on for 7Ah batteries
The DIP switches fitted to the charge control PCB, control
some of the operational features of the controller as
follows:
By default all switches are in the OFF position.
DIP switch 2
sets the charge rate. set to OFF for max
300mA charge, this is the default max. Set to ON for
100mA charge, this setting is typically used in conjunction
with the TOC-625 controller fitted with more than 4
detectors to limit the battery charge rate due to the smaller
size of the TOC-625 PSU.
Note that the DIP switch setting is only read at power up.
The system must be powered on and off (batteries
disconnected) before the new setting takes effect.
1. Connect the batteries allow system to power up on battery power
For a new installation.
2. Switch on the mains power to the control panel
During this process observe the LED status and see the battery charge status
then the switch over from battery power only to mains and battery charge.