5.6 Editing The Channel Description
5.7 Change Channel
5.75 Common Alarms
1 O2 0 % VOL
DESCRIPTION
1 O2 0 % VOL
1 O2 0 % VOL
ROOM 3
ROOM 3
Rotating the jog wheel causes the current
character to change. Once the desired
character is displayed press the jog wheel
to accept it and move on to the next
character to be edited. Once the desired
text string is complete press and hold in the
jog wheel. The display will flash to indicate
the end of text edit mode. Release the jog
wheel and the newly edited text string is
accepted.
Select DESCRIPTION from the user menu.
This allows the user to edit the description shown
when the unit is in normal display mode. This
description is also used in Alarm indication to
show alarm locations.
Allows the user to change channel being edited. This allows the user to stay in the menu system
rather than going out and coming back in. Press the jog wheel until the desired channel number is
displayed. Press the jog wheel to then move to that channel.
This function allows the alarm activation of a relay output from a number of grouped channel
alarms (AL1,2 or 3).
01 FROM = 1 TO =6
AL1 RELAY = 4201
Common Alarm
group Number
up to 16 groups
can be stored
Range of channels Selected
Alarm Level for the
range of selected
channels
Relay Output (in this example
an addressable relay output)
In this example for common
alarm group 1 any Alarm
level 1 that activated for
channels 1 to 6 on the
control panel will activate
relay output 4201 (this
would be an addressable
relay output in this
instance).
Note relays used in grouped functions should ideally not
be used elsewhere in the setup for individual alarm
outputs.
Page 29 of 52