background image

TOCSIN 

i

700

INSTALLATION

AND 

USER INSTRUCTIONS

Triton House
Crosby Street
Stockport
SK2 6SH
England

Tel: +44 (0)161 483 1415

Fax: +44 (0) 161 484 2345

Email: [email protected]

Website: www.internationalgasdetectors.com

FS646773

REF: ROS 66-8 V10.1

EMS696504

Содержание TOCSIN i700

Страница 1: ...INSTRUCTIONS Triton House Crosby Street Stockport SK2 6SH England T el 44 0 161 483 1415 Fax 44 0 161 484 2345 Email sales internationalgasdetectors com Website www internationalgasdetectors com FS64...

Страница 2: ...y Cards Testing Addressable Relays Modbus Common Alarms Copy Alarms FIND Command Mimic Panels Battery Backup Run Time Alarm Actions User Menu Password 100 Zero Calibrate Command Channel Setup Powering...

Страница 3: ...effect requirements Failure to do so will result in an ineffective system Power Source 88 to 132V AC 110V AC Selected or 176 to 264V AC 230V AC Selected Display 2 x 16 backlight LCD Operating Temperat...

Страница 4: ...low voltage supply systems for equipment with rated current 16 A per phase Electrical apparatus for the detection and measurement of flammable gases general requirements and test methods Electrical a...

Страница 5: ...Indicates Voltage Input as Shipped From Factory By Default 230V AC Use Switch to Change if Necessary Page 5 of 52 IMPORTANT When first powering systems which include an IGD battery backup the batterie...

Страница 6: ...rgised on power up Addressable control panel versions only See Addressable Sensors Section 24V DC 24V DC AUDIO OUTPUT VISUAL OUTPUT SOUNDER O P WARNING LAMP O P Enclosure Ground Enclosure Ground 1 5mm...

Страница 7: ...T106P Pellistor Flammable Gas Detectors 1 5mmSQ See Panel for recommended cable types Max cable run 1000M 0V DC 4 20mA IN 24V DC GND ZERO FAULT CAL 360 CHASS 24V DC B A GND mA P Y W Common Active Comp...

Страница 8: ...ital Port Located at the top edge of the Tocsin 700 card is a 4 way connector used to allow digital interface to the Tocsin 700 operating system as follows 0V common Password Inhibit Reset Alarms Inhi...

Страница 9: ...to Tocsin 103 2 wire Detector Series Tocsin 700 Interface wiring continued Enclosure Ground 4 20mA Toxic And Oxygen Gas Detectors 1 5mmSQ See Panel for recommended cable types Typical max cable run 5...

Страница 10: ...1 5mm SQ cable for analogue systems Fit 2 5mm SQ cable for addressable systems Use Pirelli LSX type cable for office light commercial un zoned installations Steel Wire Armored or CY cable for medium h...

Страница 11: ...N Gas Detectors DIP Switches For Relay O P And Sounder O P Enable Sensitivity Adjustment Factory Preset Do Not Adjust 1 5mmSQ See Panel for recommended cable types Typical max cable run 500M 0V DC 24V...

Страница 12: ...E CHANNEL IS SELECTED AS A FIRE AS A GAS TYPE RELAY OUTPUTS MUST BE SET AS LATCHING NOTE THAT THE POWER IS SUPPLIED TO THE INPUT CONNECTORS IN BANKS OF FOUR IF MIXING WITH GAS DETECTORS SEGREGATE THE...

Страница 13: ...Classification 24V SCREEN SCREEN Rx 24V 24V Tx 4 20 B B A A 0V 0V 0V Tocsin 102 Addressable Series Detector Head Red White Yellow Blue Black Local Comms Connector For Palm Connection 24V SCREEN SCREE...

Страница 14: ...ea Classification 24V DC B A GND GND ZERO FAULT CAL 360 CHASS 24V DC B A GND mA P Y W Common Active Compensator ZERO FAULT CAL 360 CHASS 24V DC B A GND mA P Y W Common Active Compensator ZERO FAULT CA...

Страница 15: ...HASS PALM Set Address 24V DC B A GND mA 4300 PWR M EN Al COMM CHASS PALM Set Address MUTE ALARM MUTE ALARM 24V DC B A GND mA 4301 PWR M EN Al COMM Addressable Relay Outputs These come equipped with tw...

Страница 16: ...inter Optional Keyswitch Tocsin 700R 19 rack versions of the control panel are 24V DC powered and only interface as addressable systems The systems are shipped with an addressable relay card mounted t...

Страница 17: ...with relays First Relay on The Card relays number from this one Base Address set up LED s and interface for the relay card In all Cases Relay contact ratings 7A 250V AC Non Inductive 7A 30V DC Non Ind...

Страница 18: ...relays is a dedicated system fault relay See later programming details regarding alarm and fault relays TOCSIN i700 Relay Outputs Normally Closed Common Normally Open Normally Closed Common Normally O...

Страница 19: ...and NOT powered from the Tocsin 700 with the exception of beacons and sounders Connecting third party devices which may place unknown power demands on the Tocsin 700 can result in damage and or unint...

Страница 20: ...nce etc The Tocsin 700 series gas detector control panels are designed to be as flexible in operation as possible The system software allows the owner installer to configure the following functions Co...

Страница 21: ...tted The user programmed description for the sensor is displayed Pressing the jog wheel will accept the indicated alarm If there is more than one alarm tripped then the next alarm is indicated on the...

Страница 22: ...240 minutes Normal display mode Time is user programmable in seconds and is programmed in the engineering mode Again the user can add a further two measurement types Normal display shows current chan...

Страница 23: ...he back light illuminates and the unit stops it s auto scrolling function If no channel is selected or if the button is not rotated within a minute then the unit returns to it s normal auto scrolling...

Страница 24: ...elect from 1 to 64 select from 1 to 64 2 Select I O Cable 1 or 2 Press and hold down the jog wheel The system will request a password Once entered correctly the following menu sequence will be display...

Страница 25: ...nter up to 8 character description ENABLE DISABLE PASSWORD CODE 100 SELECT GROUP FROM CHANNEL TO CHANNEL ALARM SET RELAY OP 1 to 16 1 to 37 or address AL1 AL2 or AL3 Select the from to range for the c...

Страница 26: ...or FAILED If the zero operation passed the zero correction is applied 1 O2 0 VOL CALIBRATING This function allows the user to calibrate a channel As in the case of the zero function select a channel t...

Страница 27: ...numbers 1 to 3 are included on the main panel located as shown here Cable Number 1 or 2 For Addressable Detectors and Relays Note this is not relevant for Analogue Detectors or On board Relays Relay...

Страница 28: ...channels Rotate the jog wheel if you wish to select a different channel to be copied from Once the selection is correct press the jog wheel Select the COPY ALARM SETUP menu item and the following setu...

Страница 29: ...s Allows the user to change channel being edited This allows the user to stay in the menu system rather than going out and coming back in Press the jog wheel until the desired channel number is displa...

Страница 30: ...common alarm DON T also use that relay on a normal channel alarm doing so runs the risk that a channel in the common alarm group can be trying to set a relay whilst an individual normal channel alarm...

Страница 31: ...ital Inputs COPY CH SETUP COPY FROM CH select from 1 to 64 TO RANGE CH select from 1 to 64 select from 1 to 64 FIND ADD SENSORS FIND ADD RELAYS EDIT LOW ADDRESS enter start address EDIT HIGH ADDRESS e...

Страница 32: ...wheel when correct MINUTE rotate jog wheel to change press jog wheel when correct DAY rotate jog wheel to change press jog wheel when correct MONTH rotate jog wheel to change press jog wheel when corr...

Страница 33: ...4 20OUT CAL TEST 4 20mA OUT TEST ADD SENSORS TEST ADD RELAYS TEST ADD RELAYS2 TEST RELAYS TEST FIRE CHANGE CHANNEL USER MENU EXIT TEST 4 20mA OUT 3 SET NUM BOARDS 0 to 4 SET NUM BOARDS 0 to 4 PASSWOR...

Страница 34: ...Cable Number 1 or 2 For AddresNote this is not relevant for Analogue Detectors Range Digital addressable detectors wired to port C1 and C2 have addresses starting at 4100 Up to 32 detectors can be wi...

Страница 35: ...FROM channel number is flashing This is the channel who s setup you wish to copy to other channels Rotate the jog wheel if you wish to select a different channel to be copied from Once the selection i...

Страница 36: ...default alarm levels set automatically as part of the FIND function 1 2 3 Select the FIND ADD SENSORS menu item and the following setup screen is displayed Use the jog wheel to enter the first addres...

Страница 37: ...se detectors into the panel setup or select ABORT to exit the FIND option and make no changes If you select to ACCEPT the found detectors the system will indicate sequentially each address that has be...

Страница 38: ...g is SENSORS then it is checked if not then it is ignored as in this example Select the FIND ADD RELAYS menu item and the following setup screen is displayed FOUND 4 NO CHANGES MADE 1 of 4 4201 C1 The...

Страница 39: ...r than 0 5 errors indicates an electrically noisy industrial environment or potentially faulty detector or cable terminations Up to 0 5 errors can be tolerated Normally errors can be traced to poor el...

Страница 40: ...line of the display shows the relay output that relates to the address shown on the top line of the display Press the jog wheel to change the relay status Note that the relay status set will remain un...

Страница 41: ...FLAM 5 LEL Checking 29 32 CHANGE CHANNEL In this mode of operation the following display is indicated with a 30 minute count down timer indicated on the bottom line of the display Whilst in this mode...

Страница 42: ...to add a custom UNIT to the selectable list of UNITS for example PPM VOL etc Input and store any 3 digit reference and it is added to the list of unit types that can be selected Set the Level for Fau...

Страница 43: ...g Alarms Alarm Set Point Alarm Set Point Alarm O P On Re Set Input On Alarm O P Off Re Set Input Off 5 of Alarm Set Point Alarm Activates Alarm Activates 10 Seconds Software Adjustable 10 Seconds Alar...

Страница 44: ...ls As indicated connect A B and GND 0V only CABLING REQUIREMENTS USING REMOTE MIMIC PANELS Detectors Connected to Master Panel Master Control Panel Mimic Panel Note that the detectors in this example...

Страница 45: ...24V DC B A GND 24V DC B A GND ZERO ZERO FAULT FAULT CAL CAL 360 360 CHASS CHASS 24V DC 24V DC B B A A GND GND mA mA P P Y Y W W Common Common Active Active Compensator Compensator ZERO ZERO FAULT FAUL...

Страница 46: ...cated in the overview diagram The batteries are shipped ready charged for operation Connect the battery to the charge management PCB with the cable provided Charge Control PCB Status LED s Note these...

Страница 47: ...ed if required The LED s will indicate the charge level as the battery is being re charged If the Mains power LED is off then the battery pack is active and providing backup power to the TOCSIN 700 co...

Страница 48: ...ting is typically used in conjunction with the TOC 625 controller fitted with more than 4 detectors to limit the battery charge rate due to the smaller size of the TOC 625 PSU Note that the DIP switch...

Страница 49: ...Alarm Typical Example 0 15A 1 0 15Amps Tocsin 102 IR HC Detector 0 05Amps 4 0 2Amps Total System Current 0 7 Amps The batteries used are 1 2AH units so using the previously indicated de rating factor...

Страница 50: ...n 102 Pellistor HC Detector 0 13Amps NA Tocsin 102 Toxic Gas Detector 0 02Amps NA Audible Alarm Typical Example NA 0 12A Additional Relay Units 8 16 Per Card NA 0 01A Relay Visual Alarm Typical Exampl...

Страница 51: ...t3 Fault Bit4 Sensor Disabled Bit5 Sensor Fault Bit6 Under Range Fault Bit7 Over Range Fault Bit9 Spare Bit10 Spare Bit11 Spare Bit12 Spare Bit1 AL2 Bit13 AL1 Muted Bit14 AL2 Muted Bit8 Comms Fault Bi...

Страница 52: ...t significant byte transmitted first 15 Inter byte spacing Maximum 1 5 bytes times 781uS 19200 Baud 16 Inter packet spacing Minimum 3 5 bytes times 1823uS 19200 Baud 1 1 24V DC B A 0V DC 24V DC Pin 3...