The Alarm Relay Setup Menu
The alarm relay setup on the Tocsin 750 controller is based on the relay rather than the
detector/channel. For each relay output connected on the system the following set up page must
be configured to allow the system to determine when a relay is triggered.
Set the alarm relay TYPE as:
DISABLED
AL1
AL2
AL3
AL1
or
AL2
or
AL3
AL1
and
AL2
FAULT
Set the Relay Address
Set the Cable Number onto which the Relay
is Installed
Set if the Relay is to be Energised or
De-Energised on Alarm Activation
Set if the Relay can be Muted
or not From the Control Panel
Use the FROM - TO boxes to select
groups of sensors, for example From
sensor channel 1 To sensor channel 6 to
activate this relay on alarm. Up to 7
sensor groups can be defined in this
way. Note in all cases that for these
groups of sensors the relay will be
active only for whichever alarm level,
AL1,2 or 3 is defined in the relay TYPE.
In addition to the FROM - TO sensor groups,
individual channels can also be added into the relay
activation definition. Up to 14 individual sensor
channels can be added to the definition. Note in all
cases that for these sensors channels the relay will
be active only for whichever alarm level, AL1,2 or 3 is
defined in the relay TYPE.
Use the return key to save
changes and the ESC key to exit
without making any changes.
Navigate either by typing the
relay number or using the left
and right keys.
Use to Disable Relays
Use to Save the Relay Setup