SmartModul CR2512
18
Index
S-Idx
Designation
Type
Default
Description
2004
3
max� current
channel 1, 2
u16, rw
0xFA0
max� possible load current in mA (=
current at 1000‰ PWM)
2005
0
Control parame-
ters channel 3, 4 u8, ro
0x03
Number of the entries
(= number of the control parameters)
2005
1
P-Anteil Kanal
3, 4
u8, rw
0x32
P value of the current control function
channel 3, 4 (= value in % referred to the
presetactual value difference)
2005
2
I value channel
3, 4
u8, rw
0x14
I value of the current control function
channel 3, 4 (= value in % referred to the
presetactual value difference)
2005
3
max� current
channel 3, 4
u16, rw
0xFA0
max� possible load current in mA
(= current at 1000‰ PWM)
2006
0
Control parame-
ters channel 5, 6 u8, ro
0x03
Number of the entries
(= number of the control parameters)
2006
1
P value channel
5, 6
u8, rw
0x32
P value of the current control function
channel 5, 6 (= value in % referred to the
presetactual value difference)
2006
2
I value channel
5, 6
u8, rw
0x14
I value of the current control function
channel 5, 6 (= value in % referred to the
presetactual value difference)
2006
3
max� current
channel 5, 6
u16, rw
0xFA0
max� possible load current in mA (=
current at 1000‰ PWM)
2007
0
Control parame-
ters channel 7, 8 u8, ro
0x03
Number of the entries
(= number of the control parameters)
2007
1
P value channel
7, 8
u8, rw
0x32
P value of the current control function
channel 7, 8 (= value in % referred to the
presetactual value difference)
2007
2
I value channel
7, 8
u8, rw
0x14
I value of the current control function
channel 7, 8 (= value in % referred to the
presetactual value difference)
2007
3
max� current
channel 7, 8
u16, rw
0xFA0
max� possible load current in mA (=
current at 1000‰ PWM)
20F0
20F1
0
Setting of the
Node ID
u8, rw
0x20
(= 0d32)
The node ID used to access the module
in the CANopen network�
20F2
20F3
0
Setting of the
Baud rate
u8, rw
0x04
Baud rate of the CAN network
0 = 1000 kBaud
1 = 800 kBaud
2 = 500 kBaud
3 = 250 kBaud
4 = 125 kBaud (default)
5 = 100 kBaud
6 = 50 kBaud
7 = 20 kBaud
The entries 20F0/20F1 and 20F2/20F3 must always contain identical values� The new entries are valid after
a reset (switching the module off/on)�
Values outside the permissible ranges will be rejected�