Communication Profile Area; index 1000 to 1FFF
Index
S-Idx
Designation
Type
Default
Description
1000
0
Device type
u32, ro
0x000B0191 Profile 401;
Inputs and outputs, binary and analogue
1001
0
Error register
u8, ro
0x00
Bit-coded to profile 301, the following is
supported:
0b 0000 0000 no error
0b 0000 0001 generic error
0b 0001 0000 communication error
0b 1000 0000 manufacturer specific
1003
0
Pre-defined
errorfield
u8, ro
0x02
An error list with 1 entry is supported�
1003
1
Error history
u64, ro
0x00
Error occured, coded according to
the EMCY list, the last error is in the
subindex 1�
1005
0
COB-ID
synch objekt
u32, rw 0x00000080
- Module generates no synch message
(bit 30 = 0)
- 11-bit identifier system (bit 29 = 0)
- Identifier of the synch message
1006
0
Communic�
Cycle
u32, rw 0x00000000 Max� time between 2 synch objects in
µs Useful resolution = 1ms
1008
0
Device name
str, ro
CR2512
Device name
1009
0
HW Version
str, ro
x�x
Hardware version
100A
0
SW Version
str, ro
x�x
Software version
100C
0
Guard time
u16, rw 0x0000
Time in ms
Within this time the output module ex-
pects a "node guarding" of the network
master�
If the value 0 is entered here, this func-
tion is not supported� Note:
Node monitoring with "node guarding"
or "heartbeat" can only to be used as an
alternative�
100D
0
Life time factor
u8, rw
0x00
If no "node guarding" is received for
"guard time" x "life time", the module
switches the outputs off�
The module changes the CANopen
status to PREOP�
The result from "guard time" x "life time"
must be between 0 and 65535�
1010
0
Number of save-
options
u8, ro
0x01
Number of the "save" options
1010
1
"Save all para-
meters”
u32, rw 0x02
Automatic saving of all changed para-
meters OFF/ON�
0 = AutoSave OFF
2 = AutoSave ON