10 Operation
After power on, the unit is in the Run mode (= normal operating mode)� It carries
out its measurement and evaluation functions and provides output signals
according to the set parameters�
Operation indication → chapter 7 Operating and display elements.
10.1 Read the set parameters
►
Press [Mode/Enter] until the requested parameter is displayed�
►
Briefly press [Set]�
> The unit displays the corresponding parameter value for approx� 15 s� After
15 s it again displays the parameter, then it returns to the Run mode�
10.2 Change the display in the Run mode
►
Press [Set] briefly in the Run mode�
> The unit displays the current measured value in the selected type of display for
approx� 15 s:
-System pressure in the unit set in Uni�
-System pressure in % of the set scaling of the analogue output if [OU2] is
configured as analogue output�
-System pressure in % of the final value of the measuring range if [OU2] is
configured as switching output�
10.3 Self-diagnostics / fault indications
The unit has many self-diagnostic options�
• It monitors itself automatically during operation�
• It indicates warnings and faults via IO-Link and via display (even if the display
is deactivated)�
• If a fault is found, the outputs are set according to the setting of the parameters
FOU1 and FOU2 (→ 9.4.2).