8.4 Explanation of menu level 2
Uni
Standard unit of measurement for system pressure�
SELd
Display mode:
• Pressure in the unit set in [Uni]�
• Pressure in % of the set scaling of the analogue output�
ASP
Analogue start point for system pressure: measured value at which 4 mA is
provided (20 mA if [OU2] = [InEG])�
AEP
Analogue end point for system pressure: measured value at which 20 mA is
provided (4 mA if [OU2] = [InEG])�
HI
Maximum value memory for system pressure�
LO
Minimum value memory for system pressure�
COF
Zero-point calibration�
dS1*
Switch-on delay for OUT1�
dr1*
Switch-off delay for OUT1�
dS2*
Switch-on delay for OUT2, only active if [OU2] = [Hnc], [Hno], [Fnc] or [Fno]�
dr2*
Switch-off delay for OUT2, only active if [OU2] = [Hnc], [Hno], [Fnc] or [Fno]�
FOU1*
Status of output 1 in case of an internal fault�
FOU2
Status of output 2 in case of an internal fault�
P-n*
Switching logic for the outputs: pnp or npn�
dAP
Damping for switching outputs and display�
dAA
Damping for analogue output (OUT2), also has an effect on the IO-Link
process value�
diS
Update rate and orientation of the display�
CAL
Calibration function (setting the curve of measured values)�
CP1
Calibration point 1�
CP2
Calibration point 2�
SIM
Change to menu level 3 (simulation)�
rES
Restore factory setting�
* menu items not active in 2-wire operation