Output function voltage output:
Fig. 5-10
Fig. 5-11
Maximum measuring range at [ou2] = [U]
Scaled measuring range at [ou2] = [U]
MAW
MEW
10.3
10
T [°C/°F]
U [V]
U [V]
T [°C/°F]
MEW
MAW
AEP2
ASP2
10.3
10
MAW = Initial value of the measuring range
MEW = Final value of the measuring range
ASP2 = Analogue start point
AEP2 = Analogue end point
Within the measuring range (-20...90 °C / -4...194 °F) the output signal is between
0...10 V at [ou2] = [U] or 10...0 V at [ou2] = [UnEG] (without figure).
If the temperature value (T) is outside the measuring range, the output signal
reacts as below:
[ou2] = [U]
[ou2] = [UnEG]
T < MAW (ASP2)
0 V
10.3...10 V
T > MEW (AEP2)
10...10.3 V
0 V