Doc.  No.  ITV2-OM00118-A 

 

 

 

 

 

 

 

 
 

P R O D U C T   N A M E  

E/P Regulator 

(PROFIBUS DP type) 

 

MODEL/ Series/ Product Number

 

 

ITV1000/2000/3000/2090-PR* Series 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  Install  and  operate  the  product  only  after  reading  the  Operation  Manual  carefully  and 

understanding its contents. 

 

  Specifically, read the safety instructions carefully. 

 

  Keep this operation manual available whenever necessary. 

 

Summary of Contents for ITV1000-PR Series

Page 1: ...DEL Series Product Number ITV1000 2000 3000 2090 PR Series Install and operate the product only after reading the Operation Manual carefully and understanding its contents Specifically read the safety instructions carefully Keep this operation manual available whenever necessary ...

Page 2: ...2 Handling precautions P4 Wiring method and LED indication P6 System configuration P7 Communication specification P7 Setting of dipswitch P8 Pressure setting and output monitoring P9 Communication data allocation P10 Maintenance and inspection P11 ...

Page 3: ...of equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to re...

Page 4: ... responsibility a replacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from this 1 y...

Page 5: ...l continue to operate and a humming noise will be generated Turn off the power supply when supply pressure is interrupted or shut off since the life of the product may be shortened The optional cable connector is a 4 wire type When the monitor output switch output is not being used prevent the unused wires from touching the other wires as a malfunction could occur This product is adjusted to speci...

Page 6: ...lling this product and its wiring away from strong electric fields such as those of motors and power cables etc 3 Be sure to implement protective measures against load surge for inductive loads solenoid valves relays etc 4 Turn off the power supply before inserting or removing the connector Please note that the right angled cable connector does not rotate and is limited to only one entry direction...

Page 7: ...mmunication with SELV circuit which is compliant to IEC 60950 1 electrical safety standard The communications cable recommends the use of our company PCA 1557691 PLUG The line color is when the optional cable is used Connection to external equipment LED INDICATION Item Turning ON Turning OFF RUN Power ON green Power OFF DIA Diagnostic error red Normal BF Communication error red Normal Power supply...

Page 8: ...on Item Specifications Remarks Protocol PROFIBUS DP Version DP V0 Baud rate Note 9 6k 19 2k 45 45k 93 75k 187 5k 500k 1 5M 3M 6M 12M bps Setting by master GSD File GSD SMC_1412 GSD Occupied area IN 16bit 2Byte OUT 16bit 2Byte DIAG 56bit 7Byte Lower 2 bit of 7th byte Communication data resolution 12bit 4096 resolution Output pressure condition at communication error Clear Output pressure become zer...

Page 9: ...the reverse order of the above procedure Tightening torque 0 6 to 0 8Nm Selection of ADDRESS setting mode Node address of the product can be set by software mode SW and hardware mode HW When software mode is selected the node address is set by the communication master Setting range is 1 to 125 The device supports Set_Slave_Address_Supp function But the no further changed allowed function is not in...

Page 10: ... using 12bit as F S to the electro pneumatic regulator through the master PLC e g entering a target value to the output word data area Set Date 0000h 0FFFh a F S 4095 HEX Output pressure 0 F S 100 F S a EX To set pressure at 0 3MPa by ITV2030 for 0 5MPa type 0 3MPa 0 5MPa 4095 2457 DEC 999 HEX Pressure of 0 3MPa is set by sending input data of 999 to the electro pneumatic regulator through the mas...

Page 11: ...ernal diagnostic error 0 No error 1 Error Over range error 0 No error 1 Error note The I O data occupies 2bytes 16bit respectively The pressure is set output or is monitored input by the data of b15 b1 b0 Subordinate position 12bit b11 b0 corresponds to 100 FS of pressure The pressure setting is assumed that data 1332h of 120 FS is a limit value The accuracy guarantee is to 100 FS It might respons...

Page 12: ...ncluding the switch cover Use a soft cloth to remove stains Refer to the SMC website URL http www smcworld com for more information about troubleshooting This operation manual refers to all standard types and is partially applicable to special models Revision history A P6 Add cable color 4 14 1 Sotokanda Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld co...