14
10.5 Transferring a parameter set to other sensors
1
►
Press [Mode/Enter] until [SEND] is
displayed
.
2
►
Press [Set] and keep it pressed
> [WAIT] flashes
►
Release [SET]
> [DONE] is briefly displayed, then
again [SEND]
The copying process is finished and the
parameter set of PP2001 is stored in
the sensor
Transferring a parameter set to other sensors
►
Remove the sensor from the connection cable
> [- - - -] is displayed until a new sensor is connected
►
Connect the new sensor
> [READ] is briefly displayed, then [SEND]
►
Carry out step 2
The processes can be carried out as often as desired
Finishing the copying process:
►
Press [Mode/Enter] when [SEND] is displayed
> The unit goes into the operation mode (the sensor type and then the current measured
value are displayed).
In case of communication via IO-Link with a low baud rate the operation can take one minute
or more
Error messages when carrying out the SEND action:
[ECOM] Input output error: communication error / data transfer disturbed
[EINI]
Communication error or data error; initialisation / support of the sensor not
possible
[ESEN] Sensor type error: the parameter set does not correspond to the type / measur-
ing range of the sensor
[EDAT]
Data error: at least one parameter of the internal data set is not within the valid
range of the connected sensor
The error message is displayed for 5 s Then the menu [COPY] is again active