ENGLISH
CAN KEYPAD MODULE
CPM 100
PAGE
39
Object directory
Communication profiles; index 1000 to 1FFF
Index
S-Idx
Name
Type
Default
Description
1014
0x00
COB-ID
u32, rw
0x40000080
- The module does not react
EMCY
+Node ID
on foreign EMCY mess. (bit 31 = 0)
- Module generates EMCY message
(bit 30 = 1)
- 11 Bit ID (bit 29 = 0)
- ID = 0x80 + Node ID
CAN identifier can be changed
by the user.
1016
0x00
Consumer
u8, ro
0x04
number of units monitored
heartbeat time
0x01
Consumer
u32, rw
0x00
00nn tttt tttt: monitoring time in ms
heartbeat time
nn: module number of the device
device 1
to be monitored
(if nn or tttt = 0, no monitoring)
0x02
heartbeat time
u32, rw
0x00
like Consumer heartbeat time device 1
device 2
0x03
heartbeat time
u32, rw
0x00
like Consumer heartbeat time device 1
device 3
0x04
heartbeat time
u32, rw
0x00
like Consumer heartbeat time device 1
device 4
1017
0x00
Producer
u16, rw
0x00
heartbeat time of the unit in ms
heartbeat time
1200
0x00
Server SDO
u8, ro
0x02
Number of entries
0x01
COB-ID
u32, ro
0x600 +
- SDO is valid (bit 31 = 0)
Rec SDO
Node ID
- CAN-ID of the Receive SDOs
0x02
COB-ID
u32, ro
0x580 +
- SDO is valid (bit 31 = 0)
Trans SDO
Node ID
- CAN-ID of the Transmit SDOs
1400
0x00
Receive PDO
u8, ro
0x02
Number of entries Rec PDO;
(LED status)
preset value
status LEDs
and
rows of LEDs
0x01
COB-ID
u32, rw
0x200 +
- PDO is valid (bit 31 = 0)
Rec PDO
Node ID
- CAN-ID of Rec PDOs
0x02
Trans Type
u8, rw
0x01
0x00 = synch acyclic
Rec PDO
0x01...0xF0 = synch cyclic;
The outputs are updated only after "n"
preset value
synch objects
status LEDs
n = 0x01 (1)...0xF0 (240)
and
0xFC not implemented
rows of LEDs
0xFD not implemented
0xFE = asynch man. spec. event;
outputs are updated immediately
0xFF = asynch device profile event;
outputs are updated immediately