List of parameters and EMCY objects
With the function "Restore" (see object directory, Idx 1011) the factory default
values can be restored (except for the parameters "Baud rate" and the "Node
ID"). With the next power on they become valid.
List of parameters
The life time factor 0 is interpreted as 1.
The first guard protocol is interpreted as "Start Guarding" even if guarding is not
yet active at that time (guard time = 0).
CAN KEYPAD MODULE
CPM 100
PAGE
34
Index Default
value
Change
Change
Parameter
in object
(factory preset)
saved
effective
directory
automatically
Manufacturer-specific profiles, index 2000 to 5FFF
Key configuration
2000
0x00 (push button mode)
yes
at once
Delay time keys
2001
0x00 (0 ms = Off)
yes
at once
(filter)
(valid for all keys)
Operating mode
2002
0x01
yes
at once
rows of LEDs
(red individual segment in a
row of LEDs lighting green)
Colour change point
2003
0x01
yes
at once
Flashing time 1
2004 01
0x01F4 (500 ms = 2 Hz)
yes
at once
status LED
Flashing time 2
2004 02
0x00C8 (200 ms = 5 Hz)
yes
at once
Node-ID
20F0, 20F1
0x20 (= 32)
yes
after reset
Baud rate
20F2, 20F3
0x04 (= 125 Kbits/s)
yes
after reset
Communication profiles; index 1000 to 1FFF
COB-ID SYNC
1005
0x80
yes
at once
Communication Cycle
1006
0x00 (Off)
yes
after Pre-Op
Guard Time
100C
0x00 (Off)
yes
at once
Life Time Factor
100D
0x00
yes
at once
COB-ID EMCY
1014
0x80 + Node ID
yes
at once
Heartbeat time 1
1016 01
0x00 (Off)
yes
at once
Heartbeat time 2
1016 02
0x00 (Off)
yes
at once
Heartbeat time 3
1016 03
0x00 (Off)
yes
at once
Heartbeat time 4
1016 04
0x00 (Off)
yes
at once
Producer
1017
0x00 (Off)
yes
at once
heartbeat time
COB-ID Rec PDO
1400 01
0x200 + Node ID
no
at once
Trans Type Rec PDO
1400 02
0x01 (synchronous)
yes
at once
COB-ID Trans PDO
1800 01
0x180 + Node ID
no
at once
Trans Type Trans PDO
1800 02
0xFF (asynchronous)
yes
at once