11.3 Error indications
Possible cause
Recommended measures
[Err]
Fault in the electronics.
►
Replace the unit.
[SEnS]
• Interfering sources (e.g. EMC)
• Poor cables
• Problems with the supply
voltage
►
Check electrical connection.
►
Check the connection between the
sensor and the tank ground.
[FAIL]
Error during adjustment of the
overflow prevention OP:
• Overflow prevention covered by
the medium during adjustment.
• Overflow prevention soiled.
• Minimum distances too short.
• Mounting element detected
below the overflow prevention.
• Measured value not constant.
►
Lower the level, if necessary.
►
Clean the probe.
►
Observe the notes on installation.
►
Correct the position of the overflow
prevention OP.
►
Repeat the adjustment.
►
Deactivate OP
→ 5.2.2
.
[SCx] +
LEDs 5 - 8
Flashing:
short circuit in switching output x.
►
Remove the short circuit.
[SC] +
LEDs 5...8
Flashing:
short circuit in all switching
outputs.
►
Remove the short circuit.
[PArA]
Faulty data set.
►
Reset to factory settings [rES].
11.4 Output response in different operating states
Table
11-1
OUT1...4
Initialisation phase
OFF
Overflow prevention OP not
adjusted
OFF
Overflow prevention OP adjusted
or deactivated, normal operation
According to the level and
setting [ou1]...[ou4]
Fault
OFF for [FOUx] = [OFF]
ON for [FOUx] = [On]
12 Technical data
Technical data and scale drawing at www.ifm.com.