14
6.1 Notes on installation instructions for operation with
overflow prevention
[MEdI] = [CLW..] or [OIL..],
[OP] = [value ...] (overflow prevention OP activated)
It is allowed to fix mounting elements in the mounting zone (M) (Fig. 6-1).
►
Observe the maximum permitted outside length (c) according to table 6-1.
►
Observe the minimum distances according to Fig. 6-1 and Table 6-2.
►
Observe the notes on the integrated overflow prevention OP.
The overflow prevention OP must:
1.
be below the mounting element
2.
be set at a minimum distance (y) to it
The minimum distance is measured between lower edge mounting
element and OP value.
Table
6-2
MEdI = CLW.1
MEdI = CLW.2, OIL.1
MEdI = OIL.2
[cm]
[inch]
[cm]
[inch]
[cm]
[inch]
x
2.0
0.8
3.0
1.2
4.0
1.6
u
1.0
0.4
1.0
0.4
1.0
0.4
y (LK8122)
2.5
1.0
3.5
1.4
4.5
1.8
y (LK8123)
4.5
1.8
5.5
2.2
6.5
2.6
y (LK8124)
6.0
2.4
7.0
2.8
8.0
3.2
v
4.5
1.8
4.5
1.8
4.5
1.8
w
4.0
1.6
5.0
2.0
6.0
2.4
Calculation aids for [OP]:
→ 12.3