38
15.2 Pumping station
Empty the tank / overflow prevention with 3 switching outputs
Replaces 3 float switches
Configuration of the switching outputs 1...3
SP1
Maximum value exceeded
→ alarm.
ou1
Hysteresis function, normally closed (Hnc).
SP2
Upper value exceeded
→
submersible pump ON.
ou2
Hysteresis function, normally open (Hno).
SP3
Below the lower value
→ submersible pump OFF.
ou3
Hysteresis function, normally closed (Hnc).
rP1...3 Each slightly below SPx to suppress wave movements.
L
SP1
1
0
OUT1
Hnc
1
0
OUT2
Hno
SP2
SP3
t
1
0
OUT3
Hnc
OFS
XX.X
A
B
• If the level is below SP1, the output is switched. If the level is above SP1 or if
there is a wire break, output 1 switches OFF (alarm message "overflow / wire
break“).
• If the level exceeds SP2, output 2 switches (upper value exceeded;
submersible pump ON).
• If the level is below SP3, output 3 switches (lower value reached; submersible
pump OFF).