46
Power-on delay time
< 6 s
Response time
[ms] acc� to input circuit
→
chapter
8�1
8�2
8�3
8�4
8�5
Release
40
160
40
110
110
Safety requirement
30
180
30
30
30
Ambient temperature
-25���55°C
Protection rating
IP 20
Housing materials
PA
Input characteristics (S34, S43)
"1": > 11 V, 6 mA
"0": < 5 V, < 500 µA
Output characteristics
S33 push-pull short-circuit proof
"0": I
sink
~ 30 mA
"1": I
source
≥ 50 mA, U > 18 V
S44 "0": I
R
≤ 300 µA
"1": I
source
≥ 50 mA, U > 18 V
Y7 "0": I
R
≤ 300 µA
"1": I
source
≥ 11 V @ 30 mA, ≥ 15 V @ 15 mA
Current through feedback contacts
(Y1-Y2 or Y1-Y6)
6 mA
Mission time T
M
(Mission time)
175 200 h
Safety-related reliability PFH
2�2 x 10
-9
/ h
MTTF
D
136 years
DC / CCF / Cat�
99 % / 80 % / 4
B10
D
max� 780 000
Comments
Additional comments concerning the cULus approval
(UL 508):
•
Maximum ambient temperature 55°C (in the control
cabinet)
•
The safety functions were not assessed by UL� The
approval has been made according to UL 508 for
general applications�
•
Use 60/75°C copper conductors only�
•
For use in pollution degree 2 environment
•
Same polarity (phase) referred to the output
contacts
Содержание G1501S
Страница 1: ...706199 00 04 2012 Original operating instructions Safety relay with relay outputs G1501S UK ...
Страница 16: ...16 Input circuit Output status LED display ...
Страница 17: ...17 UK Input circuit Output status LED display ...
Страница 26: ...26 LED display Cause of the fault Troubleshooting Short circuits Check wiring ...
Страница 29: ...29 UK Input circuit Output status LED display 1 Electronic fail safe sensor 1 2 Electronic fail safe sensor 2 ...
Страница 34: ...34 8 4 2 Function Input circuit Output status LED display N O contact activated ...
Страница 35: ...35 UK Input circuit Output status LED display 1 Electronic fail safe sensor 1 2 Electronic fail safe sensor 1 ...
Страница 44: ...44 LED display Cause of the fault Troubleshooting Short circuits Check wiring ...
Страница 49: ...49 UK ...