4.1 Requirements for the hardware configuration
The following requirements must be complied with when using the safety relay
G1501S:
4.1.1 Product-independent requirements
It must be ensured that the safety requirements of the respective application
correspond to the requirements stated in these instructions�
The specified technical data indicated in these instructions must be complied with�
The principle of normally closed operation must be applied to all external safety
circuits connected to the system�
By taking administrative measures in the application it must be ensured that
•
the safety relays type G1501S in operation are subjected to a self-test
(switching off) within a period of maximum 12 months (intermittent operation)
•
the safety-related relay contacts are protected using a suitable fuse of 3�6 A as
short-circuit / overload protection�
The self-test can be carried out by switching the supply voltage off and on or by a
safety request�
4.1.2 Product-dependent requirements
In case of faults within the safety relay which result in the defined safe state, the
safety relay must be replaced�
Any faulty unit should be returned to the manufacturer�
Содержание G1501S
Страница 1: ...706199 00 04 2012 Original operating instructions Safety relay with relay outputs G1501S UK ...
Страница 16: ...16 Input circuit Output status LED display ...
Страница 17: ...17 UK Input circuit Output status LED display ...
Страница 26: ...26 LED display Cause of the fault Troubleshooting Short circuits Check wiring ...
Страница 29: ...29 UK Input circuit Output status LED display 1 Electronic fail safe sensor 1 2 Electronic fail safe sensor 2 ...
Страница 34: ...34 8 4 2 Function Input circuit Output status LED display N O contact activated ...
Страница 35: ...35 UK Input circuit Output status LED display 1 Electronic fail safe sensor 1 2 Electronic fail safe sensor 1 ...
Страница 44: ...44 LED display Cause of the fault Troubleshooting Short circuits Check wiring ...
Страница 49: ...49 UK ...