background image

3

UK

1  Preliminary note

• 

An instruction is indicated by "►":

 

Example: ► Mount the unit as shown.

Important note 

Non-compliance may result in malfunction or interference�

Information 

Supplementary note

2  Safety instructions

•  Please read the operating instructions prior to set-up of the unit� Ensure that 

the product is suitable for your application without any restrictions�

•  The unit conforms to the relevant regulations and EC directives�
•  Improper or non-intended use may lead to malfunctions of the unit or to unwan-

ted effects in your application�

•  Installation, electrical connection, set-up, operation and maintenance of the unit 

must be carried out by qualified personnel authorised by the machine operator�

•  The design of the unit corresponds to protection class III (EN61010) except for 

the terminal blocks� Protection against accidental contact (safety from finger 

contact to IP 20) for qualified personnel is only ensured if the terminals have 

been completely inserted� Therefore the unit must always be mounted in a 

control cabinet of at least IP 54 which can only be opened using a tool�

•  For DC units the external 24 V DC supply must be generated and supplied 

according to the requirements for safe extra-low voltage (SELV) since this vol-

tage is provided near the operating elements and at the terminals for the supply 

of sensors without further protection measures�

3  Functions and features

•  The diagnostic electronics has 2 analogue inputs and 4 dynamic inputs� These 

inputs can be used for process value monitoring, vibration monitoring, vibration 

diagnostics or analysis of other dynamic signals�

•  An analogue current signal or a pulse signal can be connected to the analogue 

inputs� They can be used as speed input for vibration diagnostics, as trigger of 

a measurement or for process value monitoring�

Содержание efector 800 VSE002

Страница 1: ...Operating instructions Diagnostic electronics for vibration sensors VSE002 VXE002 VXE003 VYE001 VYE002 VYE003 VYE104 80226772 01 07 2019 UK ...

Страница 2: ...5 5 Electrical connection 5 5 1 Limited voltage current 6 5 2 Wiring 6 5 2 1 Wiring of the sensors 1 4 S1 S4 according to the sensor 7 5 3 Connection of the sensors 7 5 3 1 Monitoring the sensor cable 7 5 4 Ethernet connection 8 6 Operation 8 6 1 Settings 8 7 Indicators LEDs 9 8 Maintenance repair and disposal 10 9 Scale drawing 10 ...

Страница 3: ...s Protection against accidental contact safety from finger contact to IP 20 for qualified personnel is only ensured if the terminals have been completely inserted Therefore the unit must always be mounted in a control cabinet of at least IP 54 which can only be opened using a tool For DC units the external 24 V DC supply must be generated and supplied according to the requirements for safe extra l...

Страница 4: ...alogue signals for current value above and or below the limit value of up to 24 indicators objects of the dynamic signals e g vibration in the time range or frequency range FFT and or H FFT Monitoring of the objects is possible with regard to up to 2 process categories e g load and rotational speed Internal trend memory with RTC time stamp with flexible storage intervals for each object Counter fu...

Страница 5: ... 1 Installation of the sensors Adhere to the SELV criteria when the sensors are connected so that no dan gerous contact voltages are applied to the sensor or transferred to the device Sensor and diagnostic electronics supply are not electrically isolated 5 Electrical connection The unit must be connected by a qualified electrician The national and international regulations for the installation of ...

Страница 6: ...source having a secondary UL listed fuse rated a max 5 A for voltages 0 20 Vrms 0 28 3 Vp or b 100 Vp for voltages of 20 30 Vrms 28 3 42 4 Vp 5 2 Wiring 4 3 Supply L 24 V DC 20 Supply L GND 2 1 8 7 6 5 12 11 9 24 23 20 19 16 15 1 4 2 3 BN BK WH BU 4 1 3 2 BK BN BU WH OU1 switch analog OU2 switch IN 1 4 20 mA pulse IN 1 GND1 IN 2 4 20 mA pulse IN 2 GND2 22 21 18 17 14 13 10 1 4 2 3 BN BK WH BU 1 4 ...

Страница 7: ...round GND of the sensor supply The SELV criteria must therefore be met for the DC supply safety extra low voltage circuit electrically isolated from other circuits not grounded If the DC circuit is to be grounded e g due to national regulations the PELV criteria must be adhered to safety extra low voltage circuit electrically isolated from other circuits 5 3 Connection of the sensors Adhere to the...

Страница 8: ...requency range are monitored in sequence multiplex mode while the time range is monitored simultaneously Alarm states of the set objects can be displayed on up to 2 digital outputs Output 1 OU 1 can also be used as analogue output e g for transferring the total vibrations to ISO 10816 Alarm states of objects that are assigned to one of the 4 dynamic inputs sensor 1 4 are displayed by the respectiv...

Страница 9: ... Flashes green yellow alternately Teach process active LED 2 ditto for sensor 2 LED 3 ditto for sensor 3 LED 4 ditto for sensor 4 LED 5 for system Lights green System OK monitoring running Lights yellow System OK no monitoring due to parameter setting self test or FFT mode Flashes green yellow alternately Monitoring not possible faulty parameter set Flashes green red alternately System error EEPRO...

Страница 10: ...easures are necessary Only the manufacturer is allowed to repair the unit After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations 9 Scale drawing 1 Ethernet interface Technical data and further information at www ifm com ...

Отзывы: