4.2.2 Voltage output
Maximum measuring range at [ou2] = U
Measuring range scaled at [ou2] = U
MAW
MEW
10.3
10
T [°C/°F]
U [V]
U [V]
T [°C/°F]
MEW
MAW
AEP2
ASP2
10.3
10
MAW = initial value of the measuring range
MEW = final value of the measuring range
ASP2 = analogue start point
AEP2 = analogue end point
Within the measuring range the output signal is between 0 and 10 V�
If the temperature value (T) is outside the measuring range, the following output
signal is displayed:
[ou2] = U
[ou2] = U
neg
T < MAW (ASP2)
0 V
10�3���10 V
T > MEW (AEP2)
10���10�3 V
0 V
In case of internal fault, the output signal behaves according to the parameter set
in [FOU2]:
[FOU2] = On
[FOU2] = OFF
[ou2] = U
10�6 V
0 V
[ou2] = U
neg
0 V
10�6 V