prox.pad Installation/Programming Manual
4.5.5 In/Out Select
In Secured Series Front End mode, you can change set the prox.pad to record and IN or OUT event in the Secured Series Door Control
Module transaction event log. The keypad and antenna portions of the unit are programmed independently. This allows you to mount
the antenna remotely up to 10 feet away on the outside of the door and place the keypad on the inside of the door. Programming card
reader is option 16 and the keypad is option 17. The command sequence is as follows:
1. Enter Program Mode.
Press:
99 # master code *
The yellow LED blinks slowly.
2. Program the prox.pad reader for IN operation
Press:
30 # 16 # 0 # **
Program the prox.pad reader for OUT operation
Press:
30 # 16 # 1 # **
3. Program the prox.pad keypad for IN operation
Press:
30 # 17 # 0 # **
Program the prox.pad keypad for OUT operation
Press:
30 # 17 # 1 # **
4. Exit Program Mode.
Press:
*
The yellow LED stops blinking.
4.5.6 Enabling/Disabling Facility Code Matching
The “facility match required” option provides an extra level of security for Secured Series Front End card operations. This option
ensures that only cards with a facility code matching the value programmed into the prox.pad unit are processed. Cards containing
different facility codes or of the wrong type cause the unit to generate a single long beep when presented. The command sequence to
enable this feature is as follows:
1. Enter Program Mode.
Press:
99 # Master Code *
The yellow LED flashes slowly.
2. To enable facility code matching, press:
30 # 21 # 1 # **
The yellow LED continues to blink slowly.
To disable facility code matching, press:
30 # 21 # 0 # **
The yellow LED continues to blink slowly.
3. Exit Program Mode.
Press:
*
The yellow LED stops flashing.
Page 74 of 86 Document # 6055676, Rev 2.2, D4b