Electrical connection
El
ec
trical co
nn
ec
tio
n
7.5. Configuration of sensors
Sensor lines are furnished as standard with a line
cross-section of 0.75 mm².
The sensor positions are shown in the respective
installation layout. A perfect function can only be
guaranteed by a correct position and optimal thermal
transition (heat-conductive paste).
If necessary, the sensors can be extended by using
suitable cabling. Ensure a clean corrosion-free con-
nection.
7.5.1. Sensor configuration
The following sensors are included in the delivery
contents or already mounted and in any case neces-
sary (see piping scheme).
- Heat exchange sensor (B72)
factory-provided and already mounted
- Air inlet sensor (B37),
factory-provided and already mounted
-
+HDWSXPSÀRZVHQVRU%
factory provided and already mounted
- Heat pump return sensor (B34)
factory provided and already mounted
-
+*/ÀRZVHQVRU%RQO\+*/PRGHO
factory provided and already mounted
- Space heating storage tank sensor (B38)
-
&RROLQJEXႇHUVHQVRU%
- Flow sensor heating circuit A (B51)
- Hygienic sensor bottom (B41)
- Hygienic sensor top (B48)
- Warm water station sensor (B42)
- Outer sensor (B32)
(all other sensors are optional depending on the
V\VWHPFRQ¿JXUDWLRQ
The sensor lines must be laid separately
IURPWKHIHHGOLQHVVHH(0&SUREOHPV
7.5.2. Flow temperature sensor
7KHÀRZWHPSHUDWXUHVHQVRUIRUWKHKHDWLQJFLUFXLWV
used have to be installed as shown in the piping sh-
HPHV7KH\DUHPRXQWHGWRWKHDSSURSULDWHÀRZOLQHV
and connected according to the electrical connection
diagram.
7KHÀRZVHQVRUVIRUWKHKHDWLQJFLUFXLWV&*DUHFRQ
-
nected to the respective heat circuit extension mod-
ule. (see assembly instructions extension module)
7.6. Connecting the outputs
The assignment of the outputs on the central unit can
be found in the electrical wiring diagram of the heat
pump.
7.7. Grounding the system
If the protective conductor is connected properly that
means that the control panel and the housing of the
heat pump are grounded properly.
In the case of maintenance operations, ensure that
the potential equalization is restored properly once
WKHPDLQWHQDQFHKDVEHHQ¿QLVKHG
7.8. Maximum delimitation in underfloor heating
,QXQGHUÀRRUKHDWLQJFLUFXLWVDQDGGLWLRQDODSSOLFDWLRQ
thermostat has to be mounted and the appropriate
heating circuit feed has to be switched in series
above that.
If the heating circuit does not have its own heating
circuit pump (unregulated direct heating circuit), no
contact thermostat is required. The safety shutdown
of the charge pump operates in this case directly via
the heat pump.