IDEC SmartRelay installation and wiring
31
IDEC SmartRelay Manual
Remedy
To suppress this response, use an X capacitor rated at 100
nF and 2.5 kV. In a destructive situation, this type of capaci-
tor safely disconnects. You must choose the voltage level for
which the capacitor is rated such that it is not destroyed in
the case of overvoltage!
At 230 V AC, the voltage between N and an input I(n) must
not be greater than 40 V to guarantee a “0” signal. You can
connect approximately ten glow lamps to the capacitor.