Technical data
IDEC SmartRelay Manual
306
Incandescent lamp load
(25000 switching cycles) at
1000 W
1000 W
Fluorescent tubes with ballast
(25000 switching cycles)
10 x 58 W
10 x 58 W
Fluorescent tubes,
conventionally compensated
(25000 switching cycles)
1 x 58 W
1 x 58 W
Fluorescent tubes, uncom-
pensated
(25000 switching cycles)
10 x 58 W
10 x 58 W
Short circuit–proof and
overload–proof
Short–circuit current limitation
Derating
none; across the en-
tire temperature
range
none; across the en-
tire temperature
range
Short circuit–proof cos 1
Power protection
B16
600A
Power protection
B16
600A
Short–circuit proof cos 0.5 to
0.7
Power protection
B16
900A
Power protection
B16
900A
Parallel output circuits for
power increase
Not permitted
Not permitted
Protection of output relay
(if desired)
max. 16 A,
characteristic B16
max. 16 A,
characteristic B16
Minimum Switching Load
10 mA, 12 V DC
10 mA, 12 V DC
Initial Contact Resistance
100 m
Ω
maximum
(at 1A, 24V DC)
100 m
Ω
maximum
(at 1A, 24V DC)
Mechanical Life
10,000,000
operations minimum
(no load, 10 Hz)
10,000,000
operations minimum
(no load, 10 Hz)
Electrical Life
100,000 operations
minimum (rated re-
sistive load, 1800
operations / hour)
100,000 operations
minimum (rated re-
sistive load, 1800
operations / hour)
FL1D-H12RCE
FL1D-B12RCE
FL1B-M08B2R2
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com