Technical data
295
IDEC SmartRelay Manual
A.2 Technical data: FL1D-H12RCC/FL1D-
B12RCC and FL1B-M08C2R2
FL1D-H12RCC
FL1D-B12RCC
FL1B-M08C2R2
Power supply
Input voltage
100...240 V AC/DC
100...240 V AC/DC
Permissible range
85 ... 265 V AC
100 ... 253 V DC
85 ... 265 V AC
100 ... 253 V DC
Permissible mains frequency
47 ... 63 Hz
47 ... 63 Hz
Power consumption
100 V AC
240 V AC
100 V DC
240 V DC
10 ...40 mA
10 ... 25 mA
5 ... 25 mA
5 ... 15 mA
10 ... 30 mA
10 ... 20 mA
5 ... 15 mA
5 ... 10 mA
Voltage failure buffering
100 V AC
240 V AC
typ. 10 ms
typ. 20ms
typ. 10 ms
typ. 20ms
Power loss at
100 V AC
240 V AC
100 V DC
240 V DC
1.1 ...4.6W
2.4 ... 6 W
0.5 ... 2.9 W
1.2 ... 3.6 W
1.1 ...3.5W
2.4 ... 4.8 W
0.5 ... 1.8 W
1.2 ... 2.4 W
Backup of the real-time clock
at 25
°
C
typ. 80 h
Accuracy of the real-time clock typ.
±
2 s/day
Digital inputs
Number
8
4
Electrical isolation
No
No
Input voltage L1
Signal 0
Signal 1
Signal 0
Signal 1
< 40 V AC
> 79 V AC
< 30 V DC
> 79 V DC
< 40 V AC
> 79 V AC
< 30 V DC
> 79 V DC