IDEC SmartRelay functions
187
IDEC SmartRelay Manual
The thermocouples available have the following technical
data: -30 to +70
°
C, 0 to 10 VDC.
See also Chapter 4.3.6.
Configuration (example):
B3 1+
On
=+00015
Off =+00005
Protection mode
On threshold
Off threshold
Press
▲
B3 2
A
=00.10
B
=-00030
p
=0
Gain
Offset
Decimals in the message text
(if used)
View in parameter assignment mode (example):
B3 1
On
=+00015
Off =+00005
On threshold
Off threshold
Application
Internal mapping
-30 to +70
°
C = 0 to 10 V DC
0 to 1000
0
°
C
300
→
Offset = -30
Range of values:
-30 to +70
°
C = 100
1000
→
Gain = 100/1000 = 0.1
On threshold = 15
°
C
Threshold = 15
Off threshold = 5
°
C
Threshold = 5