Programming IDEC SmartRelay
IDEC SmartRelay Manual
92
3.6.9
Deleting block groups
Let us assume you want to delete the blocks B1
and
B2 from
the following circuit program (corresponds with the circuit
program in Chapter 3.6.7).
Q1
I1
I2
x
x
Par
B1
B2
Proceed as follows:
B2
Q1
1. Switch IDEC SmartRelay to programming mode
(as a reminder, refer to page 63).
2. To select '
Edit
':
Press
▲
or
▼
3. To confirm 'Edit':
Press
OK
(if required, enter your password and confirm with
OK
).
4. To select '
Edit Prg
'
:
Press
▲
or
▼
5. To confirm 'Edit Prg':
Press
OK
6. To move the cursor to the input of Q1, i.e. to B2, press :
7. Confirm with OK.
8. Now set the connector ‘x’ at output Q1 instead of block
B2. To do so:
- Select the
Co
list: Press
▲
or
▼
- Accept the Co list: Press
OK
- Select ‘
x
’: Press
▲
or
▼
- Apply ‘x’: Press
OK
Result:
Block B2 is deleted, because it is no longer used in
the circuit. This includes all blocks connected to B2. In this
example, block B1 also.
▲