17
HR6S-AB
Safety Module
HR6S-S
Safety Relay Module
• Monitors two-hand control devices (IIIA or IIIC) that are required to comply
with International Standard ISO 13851.
• IIIC can monitor two-hand pushbuttons for synchronization within 0.5
seconds.
• If one of the two buttons is released during operation, the control
sequence is canceled.
• Connects up to two input devices in parallel (except for two-hand control
devices (IIIC)). (Outputs are enabled when all inputs are enabled.)
Monitoring of Emergency
Stop circuits as per ISO
13850 and IEC 60204-1,
stop category 0
Monitoring of guards as
per ISO 14119/14120
with interlock switches
Overview of Application Functions
Safety-Related Outputs
Number of relay contacts, Normally Open, instantaneous
2
Maximum short circuit current IK
1 kA
Maximum continuous current, Normally Open relay contacts
6 A
Maximum total thermal current ∑I
THERM
12 A
Minimum current
10 mA
Utilization category as per UL 60947-5-1
B300 and R300
Utilization category as per IEC 60947-4-1 and IEC 60947-5-1
AC-1: 250 V
AC-15: 250 V
DC-1: 24 V
DC-13: 24 V
Maximum current, normally open relay contacts
AC-1: 5 A
AC-15: 3 A
DC-1: 5 A
DC-13: 3 A
External fusing
10 A, category gG
Monitoring of two-hand
control devices,
type III C
as per ISO 13851
Monitoring of proximity
switches
Monitoring of RFID
sensors
Monitoring of guards as
per ISO 14119/14120
with coded magnetic
switches
Monitoring of electro-
sensitive protective
equipment such as type
4 light curtains as per
IEC 61496-1
Additional Non-Safety-Related Outputs
Output voltage
24V DC
Maximum current
20 mA
Terminal
Part No.
Supply Voltage
Push-in terminal
HR6S-S1C
24V AC/DC
Screw terminal
HR6S-S1P
24V AC/DC
•
-
One sealing strip (see page
28
) is included with each product.
HR6S-S
Package Quantity: 1
Monitoring of two hand control devices (IIIA or IIIC)
Data Functional Safety
Defined safe state
Safety-related outputs are de-
energized
Normally Open: open
Maximum Performance Level (PL), Category (as per ISO
13849-1:2015)
Normally Open: PLe, Category 4
Maximum Safety Integrity Level (SIL)
(as per IEC 61508-1:2010)
Normally Open: 3
Safety Integrity Level Claim Limit (SILCL)
(as per IEC 62061:2005+AMD1:
2012+AMD2:2015)
Normally Open: 3
Type (as per IEC 61508-2)
B
Hardware Fault Tolerance (HFT)
(as per IEC 61508 and IEC 62061)
1
Stop Category for Emergency Stops
(as per ISO 13850 and IEC 60204-1)
0
Lifetime in years at an ambient temperature of 55 °C (131 °F) 20
Safe Failure Fraction (SFF)
(as per IEC 61508 and IEC 62061)
>99 %
Probability of Dangerous Failure per hour (PFH
D
) in 1/h
(as per IEC 61508 and ISO 13849-1)
1.13 × 10
-9
Mean Time To Dangerous Failure (MTTF
D
) in years
(as per ISO 13849-1)
2,000 (*1)
Average Diagnostic Coverage (DC
avg
)
(as per ISO 13849-1)
≥99 %
Maximum number of cycles over lifetime
DC-13
24V DC 1 A: 1200000
24V DC 3 A: 180000
AC-1
250V AC 4 A: 180000
AC-15
250V AC 1 A: 70000
250V AC 5 A: 39000
*1) According to ISO 13849-1 Annex K
Synchronization Times
The synchronization times for the synchronization of safety-related
inputs depend on the application function. (See page
18
to
19
Function
Mode Selector and Input Device Connection Example.)
For other specifications (common to all models), see page
27
.
Output expansion
possible
• See website for details on
approvals and standards.
Sa
fety Approv
ed
H
R6S
*
- 1435.IM.13500
5/2
0
TÜV NORD Systems
GmbH & Co.KG