background image

21

HR6S Safety Relay Module

Wiring Example

HR6S-DN

Function Mode Selector and Input Device Connection Example

Dial 1

Dial 2

Synchronous monitoring: No

Dynamization: Yes

Signal interlock monitoring: Yes

Synchronous monitoring: 2 s / 4 s (S12 first / S22 first)

Dynamization: Yes

Signal interlock monitoring: Yes

Emergency stop switches × 6

Interlock switches × 6

DC+ CH+ CH+

S11

S12

S13

DC+ CH+ CH+

S21

S22

S23

B

A

DC+ CH+

CH+

S31

S32

S33

DC+ CH+

CH+

S41

S42

S43

D

C

DC+ CH+ CH+

S51

S52

S53

DC+ CH+ CH+

S61

S62

S63

F

E

Dial 3

Dial 4

Synchronous monitoring: 0.5 s

Dynamization: Yes

Signal interlock monitoring: No

Synchronization: 2.2 s

Dynamization: Yes

Signal interlock monitoring: No

Interlock switches × 6

(1 NC, 1 NO)

Proximity switches × 6

(1 NC, 1 NO)

Coded magnetic switches × 6
(1 NC, 1 NO) (*1)

DC+

CH+

S11

S12

CH+

S13

DC+

CH+

S21

S22

CH+

S23

DC+

CH+

S31

S32

CH+

S33

DC+

CH+

S41

S42

CH+

S43

DC+

CH+

S51

S52

CH+

S53

DC+

CH+

S61

S62

CH+

S63

*1:  Connection examples for coded magnetic switches such as HS7A (IDEC) are also included on the instruction sheet, but certifications are not available.
Note: Status of contacts in the diagram: The status of the control switch is when it is not operated. The status of the door interlock is when the door is closed.

PLC

COM

0V

Input1

Common r

efer

ence potential

0V

Semiconductor pulse output

DC24V

K3

K4

M

14 24

HS7A-

DM

BK BU

BN+

S5 WH

S6 WH

BK

BU

BN+

HS7A-

DM

DC

AC/DC

DC+

Input

Input

Start

CH+

DC+ CH+

CH+

CH+

DC+ CH+

K1

A1

A2

S11 S12

Y1

Y2

S21 S22

Z1

B2

N(-)

K2

13

K3 K4

23

34 42

33 41

S13

S23

L1(+)

EXT

F1 F2

DC+

Input

Input

CH+

DC+ CH+

CH+

CH+

S33 S51

S61 S62

S52 S53

S63

S7

K3
K4

ESC

S2 WH

BK

BU

BN+

HS7A-

DM

DC+ CH+

CH+

CH+

S31

S41 S42

S3 WH

BK BU

BN+

HS7A-

DM

DC+

Input

Input

CH+

S4 WH

BK

BU

BN+

HS7A-

DM

S1 WH

BK BU

BN+

HS7A-

DM

S32

S43

Power 

supply

Designation

Explanation

EXT

Connector for optional 

expansion module

S1 to S6

Non-contact interlock switch

S3

Start switch

K3, K4

Contactor

PLC

Programmable controller

F1, F2

Fuse

Содержание HR6S Series

Страница 1: ...Safety Relay Modules HR6S Improve productivity with predictive maintenance of safety systems Safety Relay Modules...

Страница 2: ...echnology IoT is being promoted at factories around the world for the purpose of optimizing productivity The optimal allocation of resources and predictive maintenance are important in such factories...

Страница 3: ...Tablet Safety relay module Safety relay module 3 Advanced Diagnostic and Output Functions SAFETY RELAY MODULE HR6S Not only diagnostic results but detailed information regarding safety relat ed parts...

Страница 4: ...ging the wiring Automatic and manual operation can be selected as well as startup test which requires monitoring cross circuit detection and pre start inspection For details see page 31 Set up to 7 ty...

Страница 5: ...HR6S AK A sealing strip to secure the protective cover is included preventing the dials from inadvertent adjustment or settings from being changed Protection Outputs can be expanded excluding HR6S AB...

Страница 6: ...al input can be used to cancel the off delay and immediately cut off the output Expanded 1 output can be set to either instantaneous or delay Indicates that safety related input is activated ERROR doe...

Страница 7: ...Delay 3NO 1NC 1NO Output expansion Status output Semiconductor All diagnostic results For details see page 31 Safety related output monitor Failure detection output Number of LEDs 6 5 6 6 8 8 16 3 2...

Страница 8: ...nitoring of RFID sensors Monitoring of guards as per ISO 14119 14120 with interlock switches Monitoring of guards as per ISO 14119 14120 with coded magnetic switches Monitoring of electro sensitive pr...

Страница 9: ...es Signal interlock monitoring No Synchronous monitoring No Dynamization No Signal interlock monitoring No Synchronous monitoring 0 5 s Dynamization No Signal interlock monitoring Yes Coded magnetic s...

Страница 10: ...13849 1 1 13 x 10 9 Mean Time To Dangerous Failure MTTFD in years as per ISO 13849 1 2 000 1 Average Diagnostic Coverage DCavg as per ISO 13849 1 99 Maximum number of cycles over lifetime DC 13 24V DC...

Страница 11: ...itoring 0 5 s Dynamization No Signal interlock monitoring Yes Synchronous monitoring 0 5 s Dynamization No Signal interlock monitoring Yes 1 PNP 2 2 OSSD DC CH S11 S12 A A DC CH S21 S22 PNP PNP DC CH...

Страница 12: ...o Dangerous Failure MTTFD in years as per ISO 13849 1 2 000 1 Average Diagnostic Coverage DCavg as per ISO 13849 1 99 Maximum number of cyclesover lifetime DC 13 24V DC 1 A 1 200 000 24V DC 3 A 180 00...

Страница 13: ...toring No Dynamization No Signal interlock monitoring Yes Synchronous monitoring 0 5 s Dynamization No Signal interlock monitoring Yes Synchronous monitoring No Dynamization No Signal interlock monito...

Страница 14: ...um continuous current Normally Closed relay contacts 3 A Maximum total thermal current ITHERM 12 A Minimum current 10 mA Utilization category as per UL 60947 5 1 B300 and R300 for Normally Open contac...

Страница 15: ...1200000 with Stop Category 0 24V DC 1 A 1200000 with Stop Category 1 24V DC 3 A 180000 with Stop Category 0 24V DC 3 A 275000 with Stop Category 1 AC 1 250V AC 4 A 180000 with Stop Category 0 250 VAC...

Страница 16: ...ization No Signal interlock monitoring Yes Synchronous monitoring No Dynamization No Signal interlock monitoring Yes Synchronous monitoring 0 5 s Dynamization No Signal interlock monitoring Yes 2 PNP...

Страница 17: ...ximum current 20 mA Terminal Part No Supply Voltage Push in terminal HR6S S1C 24V AC DC Screw terminal HR6S S1P 24V AC DC One sealing strip see page 28 is included with each product HR6S S Package Qua...

Страница 18: ...ency stop switches Interlock switch Two hand control switch IIIA DC CH CH S11 S12 S13 DC CH CH S21 S22 S23 S1 S2 S11 S12 S13 DC CH CH S21 S22 S23 DC CH CH DC CH CH S11 S12 S13 S1 S2 Dial 4 Dial 5 Sync...

Страница 19: ...namization No Signal interlock monitoring Yes Synchronous monitoring No Dynamization No Signal interlock monitoring Yes Synchronous monitoring 0 5 s Dynamization No Signal interlock monitoring Yes 2 P...

Страница 20: ...e 4 light curtains as per IEC 61496 1 Terminal Part No Supply Voltage Push in terminal HR6S DN1C 24V AC DC Screw terminal HR6S DN1P 24V AC DC One sealing strip see page 28 is included with each produc...

Страница 21: ...C CH S51 S52 CH S53 DC CH S61 S62 CH S63 1 Connection examples for coded magnetic switches such as HS7A IDEC are also included on the instruction sheet but certifications are not available Note Status...

Страница 22: ...S43 PNP PNP DC CH S51 S52 CH S53 PNP PNP DC CH S61 S62 CH S63 PNP PNP Dial 7 Dial 8 Synchronous monitoring No Dynamization No Signal interlock monitoring Yes Synchronization 0 5 s Dynamization No Sign...

Страница 23: ...or delayed relay contacts Additional Non Safety Related Outputs Output voltage 24V DC Maximum current 20 mA Data Functional Safety Defined safe state Safety related outputs are de energized Normally O...

Страница 24: ...F3 33 43 51 61 34 44 52 62 23 24 AC DC DC K1 K2 A1 A2 13 14 K5 K6 K4 S2 K3 K6 K5 S1 F2 F1 L1 33 34 23 24 AC DC DC DC Input Start Input CH DC CH DC CH K1 K2 A1 A2 S11 S12 Y1 Y2 S21 S1 S22 Z1 N 13 14 K3...

Страница 25: ...rdware Fault Tolerance HFT as per IEC 61508 and IEC 62061 1 Stop Category for Emergency Stops as per ISO 13850 and IEC 60204 1 0 Lifetime in years at an ambient temperature of 55 C 131 F 20 Safe Failu...

Страница 26: ...Start switch K3 to K6 Contactor M Motor PLC Programmable controller F1 to F4 Fuse Monitoring of Emergency Stop Switch Interlock Switch Input Device Connection Example Synchronous monitoring No Dynamiz...

Страница 27: ...mm2 24 to 12 AWG Two wires without wire ferrule 1 0 2 to 1 5 mm2 24 to 16 AWG Two wires with uninsulated wire ferrule 0 25 to 1 mm2 24 to 18 AWG Two wires with insulated wire ferrule 2 0 5 to 1 5 mm2...

Страница 28: ...e rails BAA1000 Recommended ferrules Item Wire cross section mm2 Stranded wire Part No Color Package Quantitiy AWG mm2 Ferrule with insulated cover Standard pack Push in terminal For single wire 20 0...

Страница 29: ...0 g HR6S DN 99 117 a 45 EXT Weight 350 g HR6S EP Weight 200 g HR6S BAC 99 117 a 45 EXT Weight 200 g 22 5 117 99 a MOD Designation Explanation a Push in terminal 10 mm Screw terminal 5 mm EXT Connector...

Страница 30: ...l error detected Module in defined safe state ERROR LEDs 4 Configuration error detected ERROR POWER Power supply error detected LED State Explanation ERROR Snn 2 Snn 2 Cross circuit detected at safety...

Страница 31: ...c start 1 No No 6 Manual automatic start 1 Yes No 7 Monitored start 2 No No 8 Monitored start 2 Yes No 5 Automatic start when start terminals Y1 and Y2 are short circuited 6 When the switch is used to...

Страница 32: ...rify that the sensor device providing the input signal is suitable for cross circuit detection by means of dynamization If it is not use an application function without dynamization or a sensor device...

Страница 33: ...of the safe operability of the safety relay module This product is not intended for use in applications that require a high degree of safety and reliability such as nuclear power railways aviation and...

Страница 34: ...short circuit fault detection when wiring from an input device HR1S AF HR5S C2S Total width 41 DOWN Cost 45 DOWN System with off delay control system HR1S ATE Total width 52 DOWN Cost 39 DOWN HR5S C2D...

Страница 35: ...instruments or the like that could endanger life or human health ii Use in applications that require a high degree of reliability such as provision systems for gas waterworks electricity etc systems t...

Страница 36: ...IDEC Corporation All Rights Reserved EP1796 0 USA IDEC Corporation EMEA APEM SAS China IDEC Shanghai Corporation IDEC Izumi H K Co Ltd Taiwan IDEC Taiwan Corporation Singapore IDEC Izumi Asia Pte Ltd...

Отзывы: