2: M
ODULE
S
PECIFICATIONS
2-16
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
DC Input Specifications (Slim Type CPU Module)
CPU Module
FC4A-D20K3
FC4A-D20S3
FC4A-D20RK1
FC4A-D20RS1
FC4A-D40K3
FC4A-D40S3
Input Points and Common Lines
12 points
in 1 common line
12 points
in 1 common line
24 points
in 2 common lines
Terminal Arrangement
See CPU Module Terminal Arrangement on pages 2-19 through 2-22.
Rated Input Voltage
24V DC sink/source input signal
Input Voltage Range
20.4 to 26.4V DC
Rated Input Current
I0, I1, I6, I7:
5 mA/point (24V DC)
I2 to I5, I10 to I27:
7 mA/point (24V DC)
Input Impedance
I0, I1, I6, I7:
5.7 k
Ω
I2 to I5, I10 to I27:
3.4 k
Ω
Turn ON Time
I0 to I7:
35 µs + filter value
I10 to I27:
40 µs + filter value
Turn OFF Time
I0, I1, I6, I7:
45 µs + filter value
I2 to I5, I10 to I27:
150 µs + filter value
Isolation
Between input terminals:
Not isolated
Internal circuit:
Photocoupler isolated
Input Type
Type 1 (IEC 61131)
External Load for I/O Interconnection
Not needed
Signal Determination Method
Static
Effect of Improper Input Connection
Both sinking and sourcing input signals can be connected. If any input
exceeding the rated value is applied, permanent damage may be caused.
Cable Length
3m (9.84 ft.) in compliance with electromagnetic immunity
Connector on Mother Board
FL26A2MA
(Oki Electric Cable)
MC1.5/13-G-3.81BK
(Phoenix Contact)
FL26A2MA
(Oki Electric Cable)
Connector Insertion/Removal Durability
100 times minimum
Input Operating Range
The input operating range of the Type 1
(IEC 61131-2) input module is shown
below:
Transition
OFF Area
Input V
oltage (V DC)
26.4
15
5
0
1.2
12.4
Input Current (mA)
ON Area
Area
11.3
6.5
24
Inputs I0, I1, I6, and I7
Inputs I2 to I5 and I10 to I27
Transition
OFF Area
Input V
oltage (V DC)
26.4
15
5
0
1.2
7.7
Input Current (mA)
ON Area
Area
7
4.2
24
Input Internal Circuit
Input
Inter
nal Cir
cuit
COM
3.3 k
Ω
Input
Inter
nal Cir
cuit
COM
4.7 k
Ω
Inputs I0, I1, I6, and I7
Inputs I2 to I5 and I10 to I27
I/O Usage Limits
When using the FC4A-D20K3/S3 at an ambient temperature of 55°C in the
normal mounting direction, limit the inputs and outputs, respectively, which
turn on simultaneously along line (1).
When using the FC4A-D40K3/S3, limit the inputs and outputs, respectively,
which turn on simultaneously on each connector along line (2).
Input V
oltage (V DC)
26.4
0
100
I/O Simultaneous ON Ratio (%)
24.0
(3) 40°C
50
(2) 55°C
(1) 55°C
60 70 80
0
When using at 40°C, all I/Os can
be turned on simultaneously at
26.4V DC as indicated with line (3).
When using the FC4A-D20RK1/
RS1, all I/Os can be turned on
simultaneously at 55°C, input volt-
age 26.4V DC.
Содержание FC4A-C10R2
Страница 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Страница 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Страница 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Страница 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Страница 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Страница 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Страница 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Страница 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Страница 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Страница 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Страница 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Страница 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Страница 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...