M8032, M8036, M8042, M8046 High-speed Counter Reset Input
When M8032 or M8046 is turned on while two-phase high-speed counter 1 or 4 is enabled, the current value in D8045 or
D8051 is reset to the value stored in D8046 or D8052 (high-speed counter reset value) and the two-phase high-speed
counter counts subsequent input pulses starting at the reset value.
When M8032, M8036, M8042, or M8046 is turned on while single-phase high-speed counter 1, 2, 3, or 4 is enabled, the
current value in D8045, D8047, D8049, or D8051 is reset to 0, respectively.
M8050-M8077 Special Internal Relays for Modem Mode
M8080-M8117 Special Internal Relays for Data Link Communication
M8120 Initialize Pulse
When the CPU starts operation, M8120 turns on for a period of one scan.
M8121 1-sec Clock
While M8001 (1-sec clock reset) is off, M8121 generates clock
pulses in 1-sec increments, with a duty ratio of 1:1 (500 ms on and
500 ms off).
M8122 100-ms Clock
M8122 always generates clock pulses in 100-ms increments,
whether M8001 is on or off, with a duty ratio of 1:1 (50 ms on and
50 ms off).
M8123 10-ms Clock
M8123 always generates clock pulses in 10-ms increments,
whether M8001 is on or off, with a duty ratio of 1:1 (5 ms on and 5
ms off).
M8124 Timer/Counter Preset Value Changed
When timer or counter preset values are changed in the CPU module RAM, M8124 turns on. When a user program is
downloaded to the CPU from
WindLDR
or when the changed timer/counter preset value is cleared, M8124 turns off.
Timer or counter preset and current values can be changed using
WindLDR
without transferring the entire program to the
CPU again (see pages 7-8 and 7-10). When a timer or counter is designated as a destination of an advanced instruction, the
timer/counter preset value is also changed.
M8125 In-operation Output
M8125 remains on while the CPU is running.
M8130 High-speed Counter 1 (I0-I2) Reset Status (ON for 1 scan)
When reset input I2 is turned on while high-speed counter 1 is enabled either in two-phase or single-phase high-speed
counter mode, M8130 turns on for one scan to indicate that the high-speed counter 1 current value is reset. When reset
input special internal relay M8032 is turned on, M8130 does not turn on.
M8131 High-speed Counter 1 (I0-I2) Current Value Overflow (two-phase high-speed counter) (ON for 1 scan)
High-speed Counter 1 (I0-I2) Comparison ON Status (single-phase high-speed counter) (ON for 1 scan)
When the current value of high-speed counter 1 exceeds 65535 while two-phase high-speed counter is enabled, M8131
turns on for one scan.
When the current value of high-speed counter 1 reaches the preset value while single-phase high-speed counter is enabled,
M8131 turns on for one scan.
1 scan time
Star t
M8120
M8121
500 ms
1 sec
500 ms
M8122
50 ms
100 ms
50 ms
M8123
5 ms
10 ms
5 ms
Содержание FC4A-C10R2
Страница 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Страница 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Страница 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Страница 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Страница 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Страница 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Страница 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Страница 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Страница 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Страница 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Страница 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Страница 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Страница 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...