13: S
HIFT
/ R
OTATE
I
NSTRUCTIONS
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
13-3
SFTR (Shift Right)
Applicable CPU Modules
Valid Operands
For the valid operand number range, see pages 6-1 and 6-2.
▲
Internal relays M0 through M1277 can be designated as S1. Special internal relays cannot be designated as S1.
The quantity of bits to shift can be 1 through 15.
Since the SFTR instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction
should be used as required.
Valid Data Types
Example: SFTR
FC4A-C10R2/C
FC4A-C16R2/C
FC4A-C24R2/C
FC4A-D20K3/S3
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
X
X
X
X
X
Operand
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Data for bit shift
—
X
▲
X
—
—
X
—
—
bits
Quantity of bits to shift
—
—
—
—
—
—
—
1-15
—
W (word)
I (integer)
X
—
S1
*****
bits
**
S1
→
CY
When input is on, 16-bit data of the designated source operand S1 is shifted to
the right by the quantity of bits designated by operand bits.
The result is set to the source operand S1, and the last bit status shifted out is
set to a carr y (special internal relay M8003). Zeros are set to the MSB.
0
Before shift:
1
0
1
0
1
0
1
0 1
1
1
1
0
1
0
0
CY
M8003
MSB
LSB
S1
0
After shift:
1
1
1
1
0
0
0
0 1
1
0
0
1
0
1
1
CY
M8003
MSB
LSB
S1
Shift to the right
SFTR(W)
When
bits to shift = 1
When a bit operand such as Q (output), M (internal relay), or R (shift register) is designated
as the source, 16 points are used.
When a word operand such as D (data register) is designated as the source, 1 point is used.
M8120
REP
M8120 is the initialize pulse special internal relay.
When the CPU star ts operation, the MOV (move) instruction sets 29 to
data register D10.
Each time input I0 is turned on, 16-bit data of data register D10 is shifted
to the right by 2 bits as designated by operand bits. The last bit status
shifted out is set to a carr y (special internal relay M8003). Zeros are set
to the MSB.
SOTU
I0
S1 –
29
D1 –
D10
S1
D10
bits
2
SFTR(W)
MOV(W)
0
Before shift: D20 = 29
0
0
0
0
0
0
0
0 0
0
0
1
1
0
1
1
CY
M8003
MSB
LSB
D10
0
After first shift: D20 = 7
1
0
0
0
0
0
0
0 0
0
1
0
0
0
0
1
CY
M8003
MSB
LSB
D10
Bits to shift = 2
0
1
0
0
0
0
0
0
0 0
0
0
0
0
0
0
0
After second shift: D20 = 1
CY
M8003
MSB
LSB
D10
1
0
0
Shift to the right
Содержание FC4A-C10R2
Страница 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Страница 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Страница 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Страница 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Страница 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Страница 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Страница 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Страница 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Страница 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Страница 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Страница 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Страница 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Страница 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...