5

Troubleshooting Tips for Voltage Issues

Measurement

Expected

Problem

Possible

Possible

Result

Causes

Solutions

Too much load on

Redistribute loads

the load on circuit.

on the circuit.

High resistance

Locate high resistance

connection within

connection/device and

the circuit or at

repair/replace.

the panel.

Supply voltage

Consult power

too high/low.

company.

Current leaking 

Identify source of leakage:

from neutral to

multiple bonding points,

ground.

equipment or devices.

Unbalanced 3-

Check load balance

phase system.

and redistribute load.

Triplen harmonics

Oversize neutral to 

returning on 

impedance. Reduce

neutral in 3-phase

harmonic effect via

system.

filter or other methods.

Supply voltage

Consult power 

too high/low.

company.

High Peak Loads

Evaluate number of

on line caused by

electronic devices on

electronic equipment

circuit and redistribute

on line.

if necessary.

Supply frequency

Consult power 

too high/low.

company.

Voltage Drop (V

D

) Measurements

The SureTest measures the line voltage, applies a load on the circuit, measures the loaded
voltage, then calculates the voltage drop.  Results are displayed for 12A, 15A, and 20A
loads.  The National Electrical Code recommends 5% as the maximum voltage drop for
branch circuits for reasonable efficiency (NEC article 210-19. FPN 4).  And, the voltage
under load (V

L

) should not drop below 108VAC for reliable equipment operation.

A good branch circuit should start out with less than 5% voltage drop at the furthest recep-
tacle from the panel at the end of the cable run.  Then, each receptacle tested in sequence
towards the panel should show a steady decrease in voltage drop.  If the voltage drop is
above 5% and does not noticeably decrease as you get closer to the first device on the cir-
cuit, then the problem is between the first device and the panel.  Visually check the termina-
tions at the first device, the wiring between the device and the panel, and the circuit breaker

connections. High resistance points can usually be identified as hot spots using an infrared
thermometer or by measuring the voltage across the breaker.  If the voltage drop exceeds
5% but noticeably decreases as you nearer the panel, the circuit may have undersized wire,
too long of a cable run, or too much current on the circuit.   Check the wire to ensure that it
is sized per code and measure the current on the branch circuit.  If a voltage drop reading
changes significantly from one receptacle to the next, then the problem is a high impedance
point at or between two receptacles.  It is usually located at a termination point, such as a
bad splice or loose wire connection, but it might also be a bad receptacle.  

Troubleshooting Tips for Voltage Drop

Measurement

Expected

Problem

Possible

Possible

Result

Causes

Solutions

Too much 

Redistribute the 

load on 

load on 

the circuit.

the circuit. 

Undersized wire for 

Check code requirements

length of run.

and re-wire if necessary.

High resistance 

Locate high 

connection within 

resistance connection/

the circuit or at 

device and 

the panel.

repair/replace.

Estimated Load on Line (ELL) Measurement

The SureTest now estimates the load on a branch circuit to provide an indication of how
much capacity in the circuit remains or to quickly check if the circuit is dedicated. This
function is a rough estimate (no stated accuracy), as accurately measuring circuit current
has to be done with a clamp meter at the electrical panel. The proprietary way in which
these calculations are made allows the user to plug the unit into an outlet and quickly deter-
mine the current load on that branch circuit.

Both the distance of the SureTest from the load and branch circuit impedance will affect
accuracy. Best accuracy is obtained by positioning the SureTest in the same outlet as the
largest load on line; otherwise, try to position the SureTest between the load(s) and the
electrical panel. The maximum amperage reported by the tester is 15A. 

ASCC Measurement

The SureTest calculates the Available Short-Circuit Current (ASCC) that the branch circuit
can deliver through the breaker during a bolted fault (dead-short) condition. 

The ASCC is calculated by dividing the line voltage by the circuit’s line impedance (hot +
neutral).  Depressing the side arrow (      ) displays the worst-case scenario where all three
conductors (hot, neutral, ground) are shorted together  -- the neutral and ground provide a
lower impedance via a parallel return path.  Note that this second test will trip a GFCI.  See
the following equations for clarification.

Voltage Drop

<5%

High Voltage

Drop

6

Line Voltage
120VAC
220VAC

Neutral-Ground
Voltage

Peak Voltage
120VAC
220VAC

Frequency

108-132VAC
198-242VAC

<2VAC

Voltage

153-185VAC
280-342VAC

60HZ

High/low

High G-N

>2VAC

High/low

peak voltage

High/low 

frequency

WARNING:

Do not exceed the unit’s maximum voltage rating of 250VAC.

ND 5481-6 61-164 165 Ins  8/28/08  1:55 PM  Page 5

Содержание SureTest 61-164

Страница 1: ...circuit interrupter AFCI devices to ensure that AFCI breakers protecting the circuit have been installed correctly This test dis rupts the electrical supply if a functional AFCI is present This tool...

Страница 2: ...vi gate through the submenu use the side arrow button The Amperage A menu displays the Estimated Load on Line ELL in real time and holds the maximum amperage in the upper right of the display The main...

Страница 3: ...e current on the branch circuit If a voltage drop reading changes significantly from one receptacle to the next then the problem is a high impedance point at or between two receptacles It is usually l...

Страница 4: ...main menu The GFCI symbol in the display should be highlighted as the default test Press the side arrow button to highlight the EPD symbol Then press the GFCI button to activate the test The actual c...

Страница 5: ...ed The AFCI device should trip causing the display to blank out with the loss of power If the AFCI fails to trip the SureTest will not lose power and the display shows a dimly lit GFCI Test GFCI trips...

Страница 6: ...defective Replace AFCI High source of Check for line impedance high voltage or resistance drop Re wire circuit per AFCI manufacturer s Instructions Optional Accessories 61 183 Alligator Clip Adapter T...

Страница 7: ...Instrument has been evaluated and complies with insulation category III overvoltage cate gory III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Страница 8: ...product including but not limited to implied warranties of merchantability and fitness for a particular purpose are limited to the above The manufacturer shall not be liable for loss of use of the ins...

Страница 9: ...ncionamiento de los equipos Los riesgos personales de descarga el ctrica se originan en conexiones a tierra incorrectas tierras falsas y o ausencia de protecci n contra fallas de tierra Los incendios...

Страница 10: ...tando estas rutinas Para evitar este problema mantenga oprimido el bot n del teclado cada vez hasta que cambie el men Las mediciones tomadas por el SureTest se dividen en cinco men s principales que s...

Страница 11: ...60 Hz La tensi n pico debe ser 1 414 veces la tensi n eficaz de l nea en el caso de una onda senoidal limpia La tensi n de tierra a neutro debe ser inferior a 2 VCA En un circuito monof sico una tensi...

Страница 12: ...rceptible a medida que uno se acerca al primer dispositivo del circuito significa que el problema est entre el primer dispositivo y el tablero Verifique visualmente las ter minaciones del primer dispo...

Страница 13: ...posibles posibles Prueba de disyuntores GFCI Para probar el dispositivo GFCI SureTest crea un desequilibrio entre los conductores vivo y neutro haciendo circular una peque a corriente de fuga del viv...

Страница 14: ...ibles posibles El GFCI no GFCI El puede se dispara estar defectuoso Prueba de disyuntores AFCI S lo 61 165 El instrumento SureTest con AFCI aplica 8 a 12 pulsos de corriente en menos de medio segundo...

Страница 15: ...1000 Park Ave Sycamore IL 60178 Consejos para la resoluci n de problemas Medici n Resultado Problema Causas Soluciones esperado posibles posibles AFCI defectuoso Reemplace el AFCI Accesorios opcionale...

Страница 16: ...dichos da os y perjuicios gastos o p rdidas econ micas Las leyes estatales var an por lo que las limitaciones o exclusiones anteriores pueden no aplicarse en su caso Esta garant a le da derechos legal...

Страница 17: ...de c blage 33 61 164 61 165 61 165 GFCI AFCI RMS True S u r e e T s t SureTest Circuit Analyzer Introduction A l aide d une technologie brevet e les analyseurs de circuits SureTest regardent travers...

Страница 18: ...uton fl che lat rale L cran de Chute de tension VD affiche simultan ment le pourcentage de chute de tension avec une charge de 15 A et la tension charg e VL r sultante Ce menu a un sous menu qui affic...

Страница 19: ...es possibles 37 sion terre neutre lev e pourrait signaler une charge d s quilibr e entre les trois phases ou une distorsion harmonique sur le neutre partag Une tension terre neutre excessive peut entr...

Страница 20: ...p dance de terre lev e 0 003 pi de fil de 12 AWG 1 pour prot ger les personnes 40 39 Mesure de charge estim e sur la ligne ELL Le SureTest estime la charge sur un circuit de d rivation afin de fournir...

Страница 21: ...entiel Directive UL pour le temps de d clenchement Remarques 1 Pour tester un GFCI dans un circuit bifilaire pas de terre il faut utiliser l adaptateur de continuit de terre N 61 175 Connecter la pinc...

Страница 22: ...e disjoncteurs sur d faut d arc produisent des caract ristiques qui imitent certaines formes de production d arc De ce fait le testeur peut donner une fausse indication que l ICDA ne fonctionne par no...

Страница 23: ...de l adaptateur de continuit de terre l armoire ou au ch ssis de mat riel doit assurer un chemin la terre et en cons quence un tat de c blage normal sur le SureTest Une fois l adaptateur de continuit...

Страница 24: ...p cifiques et il est possible que vous b n ficiiez galement d autres droits lesquels varient d tat tat La garantie se limite exclusivement la r paration ou au remplacement il n est accord aucune garan...

Отзывы: