8

GFCI Testing

To test the GFCI device, the SureTest

®

creates an imbalance between the hot and neutral con-

ductors by leaking a small amount of current from hot to ground using a fixed value resistor.
The test current applied by the SureTest

®

should not be less than 6mA or greater than 9mA

per UL-1436.  A functional GFCI should sense the imbalance and disconnect the power.  The
SureTest displays the actual test current in milliamps and trip time in milliseconds.

To conduct a GFCI test, press the GFCI button to enter the GFCI main menu.  The GFCI
symbol in the display should be highlighted as the default test.  If EPD is lit, then use the
side arrow (

) to highlight the GFCI symbol.  Then, press the GFCI button to activate the

test.  The actual current being leaked to ground is displayed. The TEST icon and hourglass
symbol appear on the display to let the user know that the GFCI test is being performed.
The GFCI device should trip within the UL established guideline causing the display to
blank out with the loss of power.  When the GFCI device is reset, the unit displays the actual
trip time that the GFCI took to respond to the current imbalance and open the circuit.
Pressing the down arrow button ( ) returns it to the wiring verification mode. If the GFCI
fails to trip, the SureTest terminates the test after 6.5 seconds.  Further inspection should
determine whether the GFCI circuitry is faulty, the GFCI is installed incorrectly, or if the cir-
cuit is protected by a GFCI device.  

UL Guideline
for trip time:

Notes:  

1)  In order to test a GFCI in a 2-wire system (no ground), the #61-175 ground continuity

adapter must be used. Connect the alligator clip on the adapter to a ground source,
such as to a metal, water or gas pipe.

2)  All appliances or equipment on the ground circuit being tested should be unplugged 

to help avoid erroneous readings.

In addition to performing a GFCI test for evaluating personal protection from shock hazards,
the SureTest can also conduct testing to ensure equipment protection from ground faults
exceeding 30mA.  The method of operation is the same as the GFCI test noted in the first
paragraph above but uses a different resistor to create a 30mA leakage current from hot-to-
ground.  To conduct an EPD test on an Equipment Protective Device, press the GFCI button
to enter the GFCI main menu.  The GFCI symbol in the display should be highlighted as the
default test.  Press the side arrow (

) button to highlight the EPD symbol.  Then, press

the GFCI button to activate the test.  The actual current being leaked to ground is displayed.
The TEST icon and hourglass symbol appear on the display to let the user know that the
EPD test is being performed.  The EPD should trip causing the display to blank out with the

Where:

T = seconds (s)
I = milliamps (mA)

I

T=(

20

)

1.43

7

ASCC1 = Line Voltage (VHN)/ (Hot 

Ω

+ Neu 

Ω

)

ASCC2 = Line Voltage (VHN)/ (Hot 

Ω

+ 1/(1/Neu 

Ω

+ 1/ Grd 

Ω

)

Impedance (Z) Measurements

If the voltage drop measurement exceeds 5%, analyze the hot and neutral impedances.  If
one is significantly higher than the other, the problem is with the conductor with the much
higher impedance.  Then, check all connections on that conductor back to the panel.  If
both impedances appear high, the source can be undersized wire for the length of run, a
bad device, or poor connections at the pigtails, devices, or panel.  

The ground impedance measured should be less than 1 ohm as a rule of thumb to ensure
that fault current has a sufficient path back to the panel.  IEEE states the ground impedance
should be less than 0.25 ohms to ensure the ground conductor can safely return any fault
current which could damage equipment on the circuit.  Surge suppression systems require
a good ground to adequately protect equipment from transient overvoltages.  Note that a
small amount of current is applied to the ground conductor to accurately measure its
impedance.  By the inherent nature of this test, a GFCI protected circuit will trip unless the
device is temporarily removed from the circuit.

Troubleshooting Tips - Impedances 

Measurement

Expected

Problem

Possible

Possible

Result

Causes

Solutions

<0.0048

Ω

/foot 

Too much load

Redistribute the load

of 14 AWG wire 

on branch circuit.

on the circuit.

<0.003

Ω

/ foot 

Undersized wire

Check code requirements

of 12 AWG wire

for length of run.

and rewire if necessary.

<0.001

Ω

/ foot 

High resistance

Locate high resistance

or 10 AWG wire

connection within 

connection/device

the circuit or at

and repair/replace.

the panel.

< 1 

Ω

to 

protect people

High resistance

Locate high resistance

connection within

connection/device

the circuit or at

and repair/replace.

the panel.

Hot and Neutral

Impedance

Ground

Impedance

<0.25

Ω

to

protect 

equipment

Undersized wire

for length of run.

Check code requirements 

and re-wire if necessary.

High conductor

impedance

High ground 

impedance

ND 5481-6 61-164 165 Ins  8/28/08  1:55 PM  Page 7

Содержание SureTest 61-164

Страница 1: ...circuit interrupter AFCI devices to ensure that AFCI breakers protecting the circuit have been installed correctly This test dis rupts the electrical supply if a functional AFCI is present This tool...

Страница 2: ...vi gate through the submenu use the side arrow button The Amperage A menu displays the Estimated Load on Line ELL in real time and holds the maximum amperage in the upper right of the display The main...

Страница 3: ...e current on the branch circuit If a voltage drop reading changes significantly from one receptacle to the next then the problem is a high impedance point at or between two receptacles It is usually l...

Страница 4: ...main menu The GFCI symbol in the display should be highlighted as the default test Press the side arrow button to highlight the EPD symbol Then press the GFCI button to activate the test The actual c...

Страница 5: ...ed The AFCI device should trip causing the display to blank out with the loss of power If the AFCI fails to trip the SureTest will not lose power and the display shows a dimly lit GFCI Test GFCI trips...

Страница 6: ...defective Replace AFCI High source of Check for line impedance high voltage or resistance drop Re wire circuit per AFCI manufacturer s Instructions Optional Accessories 61 183 Alligator Clip Adapter T...

Страница 7: ...Instrument has been evaluated and complies with insulation category III overvoltage cate gory III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Страница 8: ...product including but not limited to implied warranties of merchantability and fitness for a particular purpose are limited to the above The manufacturer shall not be liable for loss of use of the ins...

Страница 9: ...ncionamiento de los equipos Los riesgos personales de descarga el ctrica se originan en conexiones a tierra incorrectas tierras falsas y o ausencia de protecci n contra fallas de tierra Los incendios...

Страница 10: ...tando estas rutinas Para evitar este problema mantenga oprimido el bot n del teclado cada vez hasta que cambie el men Las mediciones tomadas por el SureTest se dividen en cinco men s principales que s...

Страница 11: ...60 Hz La tensi n pico debe ser 1 414 veces la tensi n eficaz de l nea en el caso de una onda senoidal limpia La tensi n de tierra a neutro debe ser inferior a 2 VCA En un circuito monof sico una tensi...

Страница 12: ...rceptible a medida que uno se acerca al primer dispositivo del circuito significa que el problema est entre el primer dispositivo y el tablero Verifique visualmente las ter minaciones del primer dispo...

Страница 13: ...posibles posibles Prueba de disyuntores GFCI Para probar el dispositivo GFCI SureTest crea un desequilibrio entre los conductores vivo y neutro haciendo circular una peque a corriente de fuga del viv...

Страница 14: ...ibles posibles El GFCI no GFCI El puede se dispara estar defectuoso Prueba de disyuntores AFCI S lo 61 165 El instrumento SureTest con AFCI aplica 8 a 12 pulsos de corriente en menos de medio segundo...

Страница 15: ...1000 Park Ave Sycamore IL 60178 Consejos para la resoluci n de problemas Medici n Resultado Problema Causas Soluciones esperado posibles posibles AFCI defectuoso Reemplace el AFCI Accesorios opcionale...

Страница 16: ...dichos da os y perjuicios gastos o p rdidas econ micas Las leyes estatales var an por lo que las limitaciones o exclusiones anteriores pueden no aplicarse en su caso Esta garant a le da derechos legal...

Страница 17: ...de c blage 33 61 164 61 165 61 165 GFCI AFCI RMS True S u r e e T s t SureTest Circuit Analyzer Introduction A l aide d une technologie brevet e les analyseurs de circuits SureTest regardent travers...

Страница 18: ...uton fl che lat rale L cran de Chute de tension VD affiche simultan ment le pourcentage de chute de tension avec une charge de 15 A et la tension charg e VL r sultante Ce menu a un sous menu qui affic...

Страница 19: ...es possibles 37 sion terre neutre lev e pourrait signaler une charge d s quilibr e entre les trois phases ou une distorsion harmonique sur le neutre partag Une tension terre neutre excessive peut entr...

Страница 20: ...p dance de terre lev e 0 003 pi de fil de 12 AWG 1 pour prot ger les personnes 40 39 Mesure de charge estim e sur la ligne ELL Le SureTest estime la charge sur un circuit de d rivation afin de fournir...

Страница 21: ...entiel Directive UL pour le temps de d clenchement Remarques 1 Pour tester un GFCI dans un circuit bifilaire pas de terre il faut utiliser l adaptateur de continuit de terre N 61 175 Connecter la pinc...

Страница 22: ...e disjoncteurs sur d faut d arc produisent des caract ristiques qui imitent certaines formes de production d arc De ce fait le testeur peut donner une fausse indication que l ICDA ne fonctionne par no...

Страница 23: ...de l adaptateur de continuit de terre l armoire ou au ch ssis de mat riel doit assurer un chemin la terre et en cons quence un tat de c blage normal sur le SureTest Une fois l adaptateur de continuit...

Страница 24: ...p cifiques et il est possible que vous b n ficiiez galement d autres droits lesquels varient d tat tat La garantie se limite exclusivement la r paration ou au remplacement il n est accord aucune garan...

Отзывы: