EVOMAX - MULTILINE FLUE KITS

6

FLUE DESIGN

!

3.0 FLUE DESIGN

3.01  The following standards are relevant to the  

 

 

construction, installation & testing of flue systems.

 

BSEN 14471 

Plastic Chimneys –  

 

 

   

 

requirements and test methods

 

BSEN 1856-1 

Metal Chimneys – Requirements

 

BSEN 1859 

Metal Chimneys – Test methods

 

BS 6644   

Installation & Maintenance    

 

   

 

of gas fired hot water  

 

 

   

 

boilers 70kW – 1.8MW

3.0.2  The Flue Stack must be specified by a Flue Specialist
3.0.3  Design of the connecting flue spigot must refer to the 

 

 

dimensions of the mating collar (Fig 3.1).

3.0.4  The Polypropylene header and EPDM seal are certified  

 

to BSEN 14471. 

3.0.5  Integrity of the flue joints and safety of operation must  

 

be proven by the installer.

3.0.6  The flue resistance at ‘A’ in Figure 3.2 is not permitted to  

 

exceed the maximum static pressure specification [Pmax]  

 

quoted in Table 3.3 when operating at the maximum 

 

 

capacity.

IMPORTANT:  LEAKAGE OF FLUE PRODUCTS INTO THE ROOM WILL DEPLETE  

THE OXYGEN LEVEL & INHIBIT SAFE COMBUSTION.

3.0.7  The flue route should be planned to enable the least  

 

directional change, one elbow is recommended as  

 

depicted in Figure 3.2.

3.0.8  The flue pipe diameter must be at least 200mm, larger  

 

diameters will permit longer flue length.

3.0.9  The flue material must be suitable for condensing  

 

operation.

3.0.10  The terminal guard must prevent the ingress of objects  

 

greater than 15mm diameter to comply with EN15502. 

3.0.11  The Flue Terminal design should be selected to create the  

 

least resistance and not compromise the potential flue  

 

length. A wire mesh type is recommended with a 

 

 

14mm grid.

3.0.12  Rain ingress may be ignored as the header design  

 

enables excess water to be discharged through the  

 

condensate drain.

FIGURE 3.1 

(CASCADE HEADER INTERFACE DETAIL - FEMALE FLUE SOCKET CONNECTION)

 

 

70.0 mm

                    Sealing Ring

PR-RING 1-LIPS HR-EPDM 200 ZWART

In

side

 20

2.

mm

+0

.6 

mm

-1

.0

 mm

Cascade Header Interface Detail

Cascade Header

NOTE: Connecting flue must comply with CE approval requirements

Содержание Evomax 30

Страница 1: ...ured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature fo...

Страница 2: ...2 GENERAL CONTENTS Introduction 3 Cascade Flue Components 4 Assembly 5 Flue Design 6 Commissioning 9 Starter Kit Components 10 Extension Kit Components 12 NOTE TO THE INSTALLER LEAVE THESE INSTRUCTION...

Страница 3: ...eptable operation of any individual boiler operating at its minimum output under the influence of the total system pressure generated by the adjacent boilers There are optional system configurations t...

Страница 4: ...g clips are also provided to prevent movement of the tube connections by the influence of expansion and contraction These must be fitted to the ductwork to ensure safe operation of the system 2 2 STAR...

Страница 5: ...the 30 80 models or 100 150 models the inner tube is manufactured in Polypropylene in accordance with the cascade system Flue connectors with an aluminium inner tube must not be used 2 7 WIRE RETAINI...

Страница 6: ...ORTANT LEAKAGE OF FLUE PRODUCTS INTO THE ROOM WILL DEPLETE THE OXYGEN LEVEL INHIBIT SAFE COMBUSTION 3 0 7 The flue route should be planned to enable the least directional change one elbow is recommend...

Страница 7: ...d components A A At the maximum system capacity the static pressure generated against the flue resistance at position A must not exceed the value Pmax quoted in Table 3 3 3 3 EVOMAX CASCADE FLUE SYSTE...

Страница 8: ...600 650 0 100 200 300 400 500 600 700 800 900 1000 1100 Mass Flow Rate kg hr Volume Flow Rate mean flue temp 50C cu m hr Cascade Total System Capacity Htot kW Cascade Flow Rate Qmax Cascade Total Sys...

Страница 9: ...of each Evomax model where it differs from standard standalone operation as shown in the Evomax Installation Servicing instructions To convert Evomax operation with the Multiline flue as described th...

Страница 10: ...1 AIR INLET GRILL AL 125 80 H 85 3 1 EXTENSION PP 80x500 4 1 VALVE PP 80 150 5 1 REDUCER EXC PP 150 100 6 1 ELBOW SHORT PP 100 90 7 1 COLLECTOR PP 200x610 1x100 45 8 1 COVER PP 200 CONDENSATE 9 1 SYP...

Страница 11: ...0 150 MP 2 1 AIR INLET GRILL AL 150 100 H 85 3 1 EXTENSION PP 100x500 4 1 VALVE PP 100 150 5 1 REDUCER EXC PP 150 100 6 1 ELBOW SHORT PP 100 90 7 1 COLLECTOR PP 200x610 1x100 45 8 1 COVER PP 200 CONDE...

Страница 12: ...ADAPTER CONCENTRIC PP 80 125 MP 2 1 AIR INLET GRILL AL 125 80 H 85 3 1 EXTENSION PP 80x500 4 1 VALVE PP 80 150 5 1 REDUCER EXC PP 150 100 6 1 ELBOW SHORT PP 100 90 7 1 COLLECTOR PP 200x610 1x100 45 8...

Страница 13: ...ION 1 1 ADAPTER CONCENTRIC PP 100 150 MP 2 1 AIR INLET GRILL AL 150 100 H 85 3 1 EXTENSION PP 100x500 4 1 VALVE PP 100 150 5 1 REDUCER EXC PP 150 100 6 1 ELBOW SHORT PP 100 90 7 1 COLLECTOR PP 200x610...

Страница 14: ...NOTES 14 EVOMAX MULTILINE FLUE KITS...

Страница 15: ...NOTES 15 EVOMAX MULTILINE FLUE KITS...

Страница 16: ...tinuing improvement in the design and performance of its products The right is therefore reserved to vary specification without notice The Ideal Boilers Technical Training Centre offers a series of fi...

Отзывы: