EVOMAX - MULTILINE FLUE KITS
7
FLUE DESIGN
Evomax
Model Output Cascade System Limits
Combustion Products
Data
Model
Maximum
System
Capacity
Maximum
Permissible
Header
Pressure
‘A’
(Static)
max
rate
CO
2
min
rate
CO
2
Temperature
Max
Max
Min
Hmax
Pmax
± 0.5 ± 0.5
kW
kW
kW
Pa
%
%
C
30
7.5
400
40
9.7
9.0
72
40
10
60
15
80
20
100
25
600
80
120
30
150
37.5
30P
7.5
400
40
11.4 10.6
40P
10
60P
15
80P
20
FIGURE 3.2
(FLUE SYSTEM LAYOUT)
Customer specified components
'A'
'A'
At the maximum system
capacity the static pressure
generated against the flue
resistance at position [A]
must not exceed the value
Pmax quoted in Table 3.3.
3.3 EVOMAX CASCADE FLUE SYSTEM DATA
3.4 DESIGN PROCEDURE
1.
Determine the required total heat output. (Htot) [maximum
of 6 boilers per system].
2.
Determine the required minimum heat output.
3.
From Table 3.3 select the Evomax models required.
4.
Using Figure 3.5 read the Combustion Products Flow Rate
(Qmax) at the Total System Capacity (Htot).
5.
Record the information in Table 3.6
6.
Calculate the maximum permissible flue length at
conditions Qmax & Pmax.
L = [a – (c + d)] / b (Table 3.6)