Standards
The VPM is pre-programmed with 15 different monitoring standards and the ability to
customize event triggers.
ITIC-Default
EN50160
Minimum Start Threshold 70%
Minimum Start Threshold 40%
Maximum Start Threshold 120%
Maximum Start Threshold 120%
Duration Magnitude
Duration
Magnitude
Event
Cycles %of nominal
Event
Cycles
%of nominal
Swell 1
30
110%
Swell 1
10
120%
Swell 2
1
120%
Swell 2
10
120%
Swell 3
1
120%
Swell 3
10
120%
Minor 1
600
90%
Minor 1
2
90%
Minor 2
30
80%
Minor 2
2
90%
Major 1
2
70%
Major 1
10
85%
Major 2
2
70%
Major 2
50
40%
Major 3
2
70%
Major 3
50
40%
Major 4
2
70%
Major 4
50
40%
ANSI
EN5082-1 Residential/Commercial
Minimum Start Threshold 80%
Minimum Start Threshold 40%
Maximum Start Threshold 120%
Maximum Start Threshold 110%
Duration Magnitude
Duration
Magnitude
Event
Cycles %of nominal
Event
Cycles
%of nominal
Swell 1
60
105%
Swell 1
2
110%
Swell 2
30
106%
Swell 2
2
110%
Swell 3
1
120%
Swell 3
2
110%
Minor 1
60
95%
Minor 1
2
90%
Minor 2
30
87%
Minor 2
2
90%
Major 1
1
80%
Major 1
6
70%
Major 2
1
80%
Major 2
2
40%
Major 3
1
80%
Major 3
5
40%
Major 4
1
80%
Major 4
5
40%
18
Impulse Threshold
450 Peak v/- 50V
Range
Up to 4000V positive or negative
Magnitude Resolution
.1kV
Width Detection
6 µs at 450V threshold
Duration resolution
microseconds
THD
THD to 51st Harmonic
Accuracy
+/-(2% of r 3 counts)
Resolution
0.1%
Frequency
Range
45-65 Hz
Accuracy
+/-(0.2% + 2 counts)
Resolution
0.1 Hz
Safety Rating
CAT III 300V
Environmental Operating
32°-122°F (0-50°C)
Temperature
0-50 degrees C
Max Humidity
80% at 88°F (31°C)
Maintenance
Clean with damp cloth.
This unit has no user-serviceable parts.
For technical support call 877-201-9005.
Warranty Statement
This meter is warranted to the original purchaser against defects in material or work-
manship for a two-year period after purchase. During this warranty period, IDEAL
INDUSTRIES, INC. will, at its option, replace or repair the defective unit, subject to
verification of the defect or malfunction.
This warranty does not apply to defects resulting from abuse, neglect, accident, unau-
thorized repair, alteration, or unreasonable use of the instrument.
Any implied warranties arising out of the sale of an IDEAL product, including but not
limited to implied warranties of merchantability and fitness for a particular purpose,
are limited to the above. The manufacturer shall not be liable for loss of use of the
instrument or other incidental or consequential damages, expenses, or economic
loss, or for any claim or claims for such damage, expenses, or economic loss.
State laws vary, so the above limitations or exclusions may not apply to you. This
warranty gives you specific legal rights, and you may also have other rights which
vary from state to state.
17