Delete Events
The Delete Events option clears the Log and all event records from memory.
Highlight Delete Event and press ENTER. The unit defaults to NO. UP or DOWN
ARROW to change to YES. Press ENTER to clear the log or press LEFT ARROW to
return to the Reset/Delete Events Menu without clearing the log.
Measurement Specifications
General
Memory Size:
512 Events
Storage Method:
FIFO/Queue/Overwrite of date, time, magnitude
and durations
Sampling Method:
Continuous (128 samples per cycle)
Alarm Type:
Graphical OLED display
Certifications:
UL, CE, cUL
Size:
5.25" H X 3" W X 1.62" D
130mm x 75mm x 37mm
Weight:
8 oz. (250g)
Nominal Voltage Settings:
100/110/120/200/208/220/240
Battery:
3 X AA (IEC LR03)
Battery Life:
No battery power is consumed while on AC power
Battery Ride Through:
Approximately 10hrs at peak consumption
Fuse:
100 ma fast trip, Non-user replaceable
Voltage Event Types Detected: Swells, Sags, Dual Polarity Impulses,
Voltage Loss and %THD
Plug Configurations:
North/South America, United Kingdom,
Australia/China, Continental Europe
AC Voltage
True RMS
15V-265V
Accuracy
+/-(1% of r 3 counts)
Resolution
1V
Swell, Sag threshold
User defined 15V-265V
Magnitude Resolution
0.1V
Duration resolution
half cycle
16
Setting the Date/Date Format
In SETUP, down arrow to highlight set date.
Press ENTER to change the date or format. UP and DOWN ARROWS change the
month. Press RIGHT ARROW after to actuate the day and year. PRESS RIGHT
ARROW to hightlight the date format. UP and DOWN ARROWS alternate format
between MM-DD-YY and DD-MM-YY formats. Press ENTER while the desired for-
mat is highlighted to change the way the date is displayed.
Clearing the Log and Events
Before starting a new monitoring session, the LOG count and stored events should
be cleared. From the Set Time/Date menu, RIGHT ARROW to display the
Reset/Delete events menu. This menu gives 2 options; Reset Log or Reset Events.
Reset Log
The Reset Log option clears the count of cumulative events displayed on the
Monitor Screen while retaining individual event records in each event category.
This is useful if the event records are needed for future reference but not for current
monitoring.
Press ENTER with Reset Log highlighted to activate the count cell. The unit defaults
to NO. UP or DOWN ARROW to change to YES. Press ENTER to clear the log.
Press LEFT ARROW to escape to the Reset/Delete Events menu without clearing the
log. The Log count in the Review screen will now reflect the count of events for the
new monitoring period.
15
C
US
N12966
ND 5790-3 61-830 Instructions 10/24/07 4:13 PM Page 15