21
Installation and Servicing
FLUE OUTLET
Section 2 - Installation
CUTTING HORIZONTAL FLUE TERMINAL
(non-telescopic)
1. Measure the required cut flue length (A + 44 mm)
2. Measure from the outer terminal lip to the end of outer
tube. Mark the required cut length (A + 44 mm) around
the circumference of the outer tube and cut following the
mark to ensure it is cut square.
3. Mark and cut the inner tube 10 mm longer than the outer
tube ensure the cut is square.
4. Remove all burrs on the inner and outer tube and place a
light chamfer on the inner tube to aid with assembly.
SETTING TELESCOPIC FLUE
1. Measure the required length (A + 44 mm)
2. Pull flue apart until the desired length is achieved
ensuring the stop mark is not visible.
3. Ensure both flue seams are at the top and the flue outlet
terminal is uppermost.
4. Drill a 3.5 mm hole through the small and large outer
tube using the pilot hole on the large outer tube.
5. Secure large and small outer tube using the screws
provided.
6. Seal the joint on the out tube with the tape provided.
7. Fit the internal and external wall seals.
FITTING THE FLUE THROUGH THE WALL
(Internal Installation)
1. Measure the thickness of the wall.
2. To this measurement add 14 mm.
3. Make a mark on the flue shown as mark 1 below.
4. Make another mark on the flue a further 14 mm in shown
as Mark 2 above right.
5. Fit the external wall seal (black) to the flue terminal
ensuring it is fitted on the terminal outer lip seal.
6. Fit the inner wall seal approximately 65 mm prior to Mark 2.
2.13 CUTTING THE FLUE
7. Place the terminal end of the flue into the 127 mm core
drilled centrally and slowly apply slight pressure and
move the flue up or down or side to side. This will cause
the external wall seal to fold in and allow the flue to pass
through the wall.
8. When the inner wall seal is flush against the wall pull
back the flue until Mark 1 is flush with the inner wall
surface.
9. Hold the flue steady and push the inner wall seal
towards the wall until Mark 2 is just visible.
FITTING THE FLUE THROUGH THE WALL
(External Installation)
1. Follow steps 1 - 5 from above.
2. Push the flue through the 127 mm core drilled hole from
the outside
3. Return inside the property and fit the inner wall seal to
the flue.
4. Pull the flue internally until Mark 1 is flush with the inner
wall surface.
5. Holding the flue in this position push the inner wall seal
towards the wall until Mark 2 is just visible.
If Mark 1 is not flush with the inner wall surface and can be
seen prior to the wall surface, then the external wall seal
will have been dislodged and will require to be re-fitted. If
this situation occurs, then please start the process from the
beginning.
On completion the flue will be correctly installed as below.
IMPORTANT:
Ensure no White flue is visible between
the flue terminal and the wall.
Flue length measured from outer terminal lip
to end of outer flue
A + 44 mm
10 mm
10 mm
Mark Cut Length = “A” + 44 mm from terminal lip
A + 44 mm
+14 mm
Wall Thickness
+14 mm
Mark 2
Mark 1
10 mm
Adjust to Length =
“A” + 44 mm from terminal lip
Drill Hole
Adhere sealing tape
Mark 1 Flush with inter wall
125 mm Cored
drilled hole
Correctly sealed
wall seal
Mark 2 Flush with
the inner wall seal
Flue length measured from outer terminal lip
to end of outer flue
A + 44 mm
10 mm
10 mm
Mark Cut Length = “A” + 44 mm from terminal lip
A + 44 mm
+14 mm
Wall Thickness
+14 mm
Mark 2
Mark 1
10 mm
Adjust to Length =
“A” + 44 mm from terminal lip
Drill Hole
Adhere sealing tape
Mark 1 Flush with inter wall
125 mm Cored
drilled hole
Correctly sealed
wall seal
Mark 2 Flush with
the inner wall seal
Flue length measured from outer terminal lip
to end of outer flue
A + 44 mm
10 mm
10 mm
Mark Cut Length = “A” + 44 mm from terminal lip
A + 44 mm
+14 mm
Wall Thickness
+14 mm
Mark 2
Mark 1
10 mm
Adjust to Length =
“A” + 44 mm from terminal lip
Drill Hole
Adhere sealing tape
Mark 1 Flush with inter wall
125 mm Cored
drilled hole
Correctly sealed
wall seal
Mark 2 Flush with
the inner wall seal
Flue length measured from outer terminal lip
to end of outer flue
A + 44 mm
10 mm
10 mm
Mark Cut Length = “A” + 44 mm from terminal lip
A + 44 mm
+14 mm
Wall Thickness
+14 mm
Mark 2
Mark 1
10 mm
Adjust to Length =
“A” + 44 mm from terminal lip
Drill Hole
Adhere sealing tape
Mark 1 Flush with inter wall
125 mm Cored
drilled hole
Correctly sealed
wall seal
Mark 2 Flush with
the inner wall seal
Содержание LOGIC COMBI2 C24
Страница 62: ...62 Installation and Servicing Section 6 Benchmark to Commissioning ...
Страница 68: ...68 Notes Installation and Servicing ...
Страница 69: ...69 Notes Installation and Servicing ...