Mexico Super RS485 - RS4125 -
Installation & Servicing
INSTALLATION
11 PREPARING THE BOILER
Note.
Before placing the boiler in the selected position any gas
and water connections at the rear of the boiler should be
prepared, due to the possible lack of access.
1.
Screw the distributor tube (supplied with a 1" BSP x
28mm copper adaptor) into the selected heating return
tapping, using an appropriate jointing material.
IMPORTANT.
It is
IMPERATIVE
that the index mark on the distributor
tube bush is in alignment with the mark on the section
boss, as shown in Frame 7.
DO NOT disturb it when connecting subsequent
pipework.
Fully pumped systems using more than 1 pump,
serving separate zones, must have a common return
connection to the distributor tube.
2.
Select the desired pumped flow tapping.
3.
Screw the supplied boiler thermostat pocket into the
appropriate front section tapping, using an approved
jointing material. Refer to Tables 7 and 8.
4.
Connect pipe fittings to the rear tappings and plug any
unused tappings.
Note
.
If using iron elbows fit a short straight connector into
the boiler tapping first, to clear the casing.
Connections - as viewed at front
Thermostat Position
Back Section
Front Section
CH
DHW
Flow Return
Flow
Return
Top
LH
LH
RH
RH
LH
LH
RH
RH
LH
LH
RH
RH
LH
LH
RH
RH
LH
LH
RH
RH
Table 8 - Gravity Domestic Hot Water
and Pumped Central Heating
Table 7 - Fully Pumped Systems
Connections - as viewed at front
Thermostat Position
Back Section
Front Section
Flow
Return
Top
LH
LH
LH
LH
RH
LH
RH
RH
RH
RH
LH
RH
12 PREPARING THE WALL
1
. Cut the appropriate hole in
the wall for insertion of the
terminal assembly.
Notes.
a.
Make good the hole on
the INSIDE of the
building to the given
dimensions BEFORE
fitting the boiler, to
facilitate sealing
between the terminal
and the wall when the
boiler is in position.
b.
The terminal MUST NOT
come into contact with a
combustible material
such as that used in non-
standard construction of
timber frame and
plasterboard etc.
Boiler
Dimension A
RS485
533 mm (21")
RS4100
533 mm (21")
RS4125
600 mm (23
5/8
")
2.
Place the boiler in the selected position.
3.
Make good the brickwork around the air duct.
INST
ALLA
TION
200942-1.p65
3/4/2004, 9:24 AM
14