OSDP Reader Connection
Connecting TSL readers in OSDP mode is the same as the connection for standard RS-485 configuration.
1
2
3
4
5
6
7
8
9
0
X
L1
L2
BZ
C
D0/
D1/
NA
NB
V+
V-
Reader Connections
Color
Wire
Connection
Red
V+
12VDC positive
Black
V-
12VDC negative
Yellow
D0/NA
RS-485 A
Violet
D1/NB
RS-485 B
Shield
Shield (drain) wire. Frame grounded at one point only
Readers must also be programmed to operate in OSDP mode. For information on programming readers, see the
ICT Card Reader Configuration Guide
, available from the ICT website.
Connecting OSDP readers to Protege modules requires additional hardware configuration and system
programming. For more information, see
Application Note 254: Configuring OSDP Readers in Protege
.
For more information about OSDP support on ICT card readers, including configuring readers for secure channel
communications, see
Application Note 321: Configuring ICT Readers for OSDP Communication
.
OSDP Reader Location
As two OSDP readers can be connected to the same Protege module reader port, each OSDP reader is configured
as either an
Entry
or
Exit
reader in the
Reader location
setting of the associated smart reader record.
OSDP reader location is
not
determined by the reader address.
TSL Multi-Technology Card Reader | Installation Manual
25