background image

28

 

Protege DIN Rail 8 PGM Output Expander

 

| Installation Manual

 

 

 

Signals between the premises control unit and the receiving equipment, when not carried by wireless 
means, shall be protected by the following method: 

 

Onboard modem telco connection must be dedicated to the PRT-CTRL-DIN. 

 

Ethernet connection to the Internet Service Provider (ISP) with a fixed IP Address must be dedicated to 
the PRT-CTRL-DIN. 

 

To comply with the dual signal line transmission system requirement, both transmission lines (onboard 
modem and IP reporting) must be enabled. Signals shall be sent simultaneously to both, Report IP Service 
and Contact ID Reporting Service. 

The Report IP and Contact ID services must be programmed and enabled within the Protege System. The 
following options are required: 

 

The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start 
with the operating system. 

Refer to the section 

Contact ID 

in the ProtegeGX Operator Reference Manual (227-1500-000). 

 

The Report IP Service must be enabled as the primary communication channel, the Service Mode 
must be configured to start with the operating system, and the Reporting Protocol must be set to 
ArmorIP.  

Refer to the section 

Report IP 

in the ProtegeGX Operator Reference Manual (227-1500-000).   

 

When more than one means of signal transmission is used, loss of communication with the receiving 
system shall be annunciated at the receiver within 200 seconds. If a fault is detected on any of the signal 
transmission means, at least one of the signal transmission channels shall send a signal to the 
central-station to report the fault within 200 seconds. 

The Report IP and Contact ID services must be programmed and enabled within the Protege System.   

The PRT-CTRL-DIN is compatible with the Integrated Control Technology ArmorIP Internet Monitoring 
Receiver. Poll Time must be set to 40 seconds and the Grace Time must be set to 20 seconds. 

In the Protege System, the reporting service must be configured to 40 seconds. The following options are 
required for the service selected as Report IP type: 

 

The Poll Time must be programmed to 40 seconds. Refer to the 

Report IP | General

 section in the 

ProtegeGX Operator Reference Manual (227-1500-000) 

 

The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start 
with the operating system. 

Refer to the section 

Contact ID 

in the ProtegeGX Operator Reference Manual (227-1500-000) 

 

The Report IP Service must be enabled as the primary communication channel, the Service Mode 
must be configured to start with the operating system, and the Reporting Protocol must be set to 
ArmorIP.  

Refer to the section 

Report IP 

in the ProtegeGX Operator Reference Manual (227-1500-000).   

 

The Trouble Input Area must be armed in 24h mode. Refer to the section 

Trouble Inputs | Areas and 

Input Types 

in the ProtegeGX Operator Reference Manual (227-1500-000). 

In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a 
minimum of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the 
sequence is reached, an indication of the failure shall be made at the premises. 

In the Protege System, the reporting service selected as Contact ID must have the number of attempts 
programmed to 5 attempts. The following options are required: 

 

The Dial Attempts option must be programmed. Refer to the section 

Contact ID | Settings

 in the the 

ProtegeGX Operator Reference Manual (227-1500-000). 

 

DACT communication channel check-in time is not to exceed 24 hrs. 

 

Trouble Zone Service Test Report 

 

The Test Report Time must be programmed. Refer to the section 

Controllers | Configuration

 in the 

ProtegeGX Operator Reference Manual (227-1500-000). 

 

The Generate Input Restore on Test Input option must be enabled. Refer to the section 

Controller | 

Options

 in the ProtegeGX Operator Reference Manual (227-1500-000).   

 

The Test Report Time is Periodic option must be enabled. Refer to the section 

Controller | Options 

in 

the ProtegeGX Operator Reference Manual (227-1500-000).   

Содержание Protege PRT-PX8-DIN

Страница 1: ...Protege DIN Rail 8 PGM Output Expander Installation Manual ...

Страница 2: ...photocopied or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo are registered trademarks of Integrated Control Technology Limited All other brand or product names are trademarks or registered...

Страница 3: ...________________________ 13 8 LED Indicators ___________________________________________________________ 14 8 1 Status Indicator 14 8 2 Fault Indicator 14 8 3 Power Indicator 14 8 4 Output Indicators 15 9 Error Code Indication _____________________________________________________ 16 9 1 Error Code Display 16 10 Mechanical Diagram ______________________________________________________ 17 11 Mechani...

Страница 4: ...L294 29 16 FCC Compliance Statements ______________________________________________ 30 17 Industry Canada Statement________________________________________________ 31 18 Disclaimer and Warranty __________________________________________________ 32 19 Contact _________________________________________________________________ 33 ...

Страница 5: ...ny combination to the network over a distance of up to 900M 3000ft Further span can be achieved with the use of a network repeater module Locking a network prevents the removal substitution or addition of modules to the module network effectively preventing any tampering with the system The current features of the Output Expander include Secure encrypted RS 485 module communications 8 outputs Indu...

Страница 6: ...ms UL 827 Central Station Alarm Services CAN ULC S301 Central and Monitoring Station Burglar Alarm Systems CAN ULC S302 Installation and Classification of Burglar Alarm Systems for Financial and Commercial Premises Safes and Vaults CAN ULC S561 Installation and Services for Fire Signal Receiving Centres and Systems The National Electrical Code ANSI NFPA 70 The Canadian Electrical Code Part I CSA C...

Страница 7: ...all metal parts are connected to earth with separate copper wire or wires of the appropriate gauge 3 2 Earth Ground Connection The Protege DIN Rail Enclosure and the Protege DIN Rail Modules must be grounded to a single point earth ground For best results a cold water pipe should be used with a pipe wiring clamp If a cold water pipe is not available connect to a suitable ground connection in the i...

Страница 8: ... Connections multiple cabinets in different rooms sectors or buildings DIN Rail Enclosure Controller Earth Ground Link connection Dialer s Earth Ground Connection Module Network RS 485 N N NA and NB PRT RDM2 DIN PRT PSU DIN V Power Supply Reader Expander PRT PSU DIN Input Expander Output Expander PRT RDM2 DIN Input Expander PRT PSU DIN Input Expander Input Expander V DIN Rail Enclosure DIN Rail En...

Страница 9: ... location that will facilitate easy access for wiring It is also recommended that the Output Expander is installed in electrical rooms communication equipment rooms closets or in an accessible area of the ceiling 1 Hook the lower tabs under the bottom edge of the DIN Rail 2 Push the Output Expander against the DIN Rail mount until the upper tab clips over the upper rail 4 1 Removal The Output Expa...

Страница 10: ...eference to the module serial number The serial number can be found on the identification sticker on the side of the module Wiring AUX WIRING Min 22AWG Max 16AWG Depends on length and Current consumption For wire cable size a maximum of 5 voltage drop at the terminals of the powered device has to be observed MODULE NETWORK WIRING Recommended Belden 9842 or equivalent 24AWG twisted pair with charac...

Страница 11: ...t battery backed power supply unit capable of supplying the required voltage to all devices on the RS 485 network Warning The 12V N and N Communication input must be supplied from only ONE point Connections from more than one 12V supply may cause failure or damage to the Output Expander or device supplying network power The 330 Ohm EOL End of Line resistor provided in the accessory bag MUST be ins...

Страница 12: ...s 1 to 8 The 8 PGM Outputs each have a FORM C output relay The connection example below shows the control of an external LED indicator 1K5 OHM 12VAUX 0V LED V V NO C NC NO C NC Switching inductive loads that can produce high back EMF voltages or large voltage induced spikes can cause the Output Expander to behave unexpectedly and should be avoided A suitable isolation circuit must be installed bet...

Страница 13: ...on The address of the Output Expander is configured via programming and will require entry of the module serial number The serial number can be found on the identification sticker on the product Refer to the Protege System Controller installation manual for address programming details ...

Страница 14: ...the installer to easily identify the module in question Upon either a module update or the identification time period set expiring the module will return to normal operation 8 2 Fault Indicator The Fault indicator is lit any time the module is operating in a non standard mode State Description Flashing red Module is in boot mode awaiting firmware update On red Module is in error state and will fla...

Страница 15: ... Rail 8 PGM Output Expander Installation Manual 15 8 4 Output Indicators The Output indicators will show the status of the outputs State Description 1 Constantly on red Output is ON 1 Constantly off Output is OFF ...

Страница 16: ...with the system controller To clear this error update the module using the module update application 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within the range set on the system controller restart the module by disconnecting the power 4 Address In Use The Address is already in use by another mo...

Страница 17: ...Pass Through PGM Outputs 7 8 RS 485 Input PGM Outputs 5 6 PGM Outputs 3 4 12VDC Pass Through PGM Outputs 1 2 12VDC Pass Through 12VDC Pass Through 12VDC Input Status Indicators NC C NO NC C NO V V RELAY 8 RELAY 7 12 VDC OUT NC C NO NC C NO V V RELAY 6 RELAY 5 12 VDC OUT POWER STATUS FAULT 5 6 7 8 OUTPUT 1 2 3 4 N N NA NB V V NO C NC NO C NC 12 VDC IN RS485 NETWORK 12 VDC OUT RELAY 4 RELAY 3 V V NO...

Страница 18: ...er Installation Manual 11 Mechanical Layout The mechanical layout shown below outlines the essential details needed to help ensure the correct installation of the Output Expander 156 8m m 143 5m m 36 4m m 90mm BACK 90mm 156 8mm FRONT 44 1m m ...

Страница 19: ...rature Operating 0 50 C 32 122 F Storage 10 85 C 14 185 F Humidity 0 93 non condensing indoor use only relative humidity The Total Combined Current refers to the current that will be drawn from the external power supply to supply the Output Expander and any devices connected to the Expander s outputs The Auxiliary outputs are directly connected via electronic fuses to the N N input terminals and t...

Страница 20: ...l 8 PGM Output Expander Installation Manual 13 New Zealand and Australia General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards ...

Страница 21: ...s of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with you national legislation For business users in the European Union If you wish to discard electrical and electronic equipment please contact your dealer or supplier for further information Information on Disposal in other Countries outside the European Union This symbol ...

Страница 22: ... Set Zone Alarm nor Internals Only on Part Set Tamper Alarm should be selected To comply with EN 50131 1 Single Button Setting should not be selected To comply with EN 50131 1 only one battery can be connected and monitored per system If more capacity is required a single larger battery must be used Anti Masking To comply with EN 50131 1 Grade 3 for Anti Masking detectors with a separate or indepe...

Страница 23: ...iance Requirements CAN ULC S304 06 Auto Arming Control units that support auto arming shall provide an audible signal throughout the protected area not less than 10 min prior to the auto arming taking place The control unit shall allow authorized users to cancel the auto arming sequence and transmit such cancelation to the signal receiving center with the identification of the authorized user that...

Страница 24: ...ervice Test Report The Test Report Time must be programmed Refer to the section Controllers Configuration in the ProtegeGX Operator Reference Manual 227 1500 000 The Generate Input Restore on Test Input option must be enabled Refer to the section Controller Options in the ProtegeGX Operator Reference Manual 227 1500 000 The Test Report Time is Periodic option must be enabled Refer to the section C...

Страница 25: ...ess such can be on line at all times have a minimum 128 bit encryption scheme have encryption enabled network and domain security implemented Network access policies shall be set to restrict unauthorized network access and spoofing or denial of service attacks Internet Service Provider ISP The Internet Service Provider ISP providing service shall meet the following requirements redundant servers s...

Страница 26: ...ded cable A bell or visual indicator used as an arming acknowledgement signal must be listed to a ULC security signaling or fire standard If intended to be mounted outside it must be rated for outdoor use Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction AHJ and shall not impair the operation of panic hardware and emergency egress If fir...

Страница 27: ...ime is Periodic option must be enabled Refer to the section Controller Options in the ProtegeGX Operator Reference Manual 227 1500 000 Ethernet Connections All Ethernet network connections shall be installed within the same room as the equipment Power Supply Mains Power Connection If a flexible cord is used to connect to line voltage strain relief must be provided for the cord inside the enclosure...

Страница 28: ...econds In the Protege System the reporting service must be configured to 40 seconds The following options are required for the service selected as Report IP type The Poll Time must be programmed to 40 seconds Refer to the Report IP General section in the ProtegeGX Operator Reference Manual 227 1500 000 The Contact ID Reporting Service must be enabled and the Service Mode must be configured to star...

Страница 29: ...e protected premise and are UL 294 Listed for Attack Class I applications only Exit devices and wiring must be installed within the protected area For the Models PRT CTRL DIN and PRT RDM2 DIN all RS485 and reader terminal connections must be made using shielded grounded cable All readers must be connected with shielded grounded cable A bell or visual indicator used as an arming acknowledgement sig...

Страница 30: ...h can be deter mined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Re orient the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Changes or modifications not authorized by the p...

Страница 31: ...put Expander Installation Manual 31 17 Industry Canada Statement This class A digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe A est conforme à la norme NMB 003 du Canada CAN ICES 3 A NMB 3 A ...

Страница 32: ... under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the Integrated Control Technology policy of enhanced development design and specifications are subject to change without notice Refer to the Integrated Control Technology website http www ict co for the latest information For warranty information see our S...

Страница 33: ...on below Integrated Control Technology P O Box 302 340 North Harbour Post Centre Auckland New Zealand 4 John Glenn Ave Rosedale North Shore City 0632 Auckland New Zealand Phone 64 9 476 7124 Toll Free Numbers 0800 ICT 111 0800 428 111 New Zealand 1800 ICT 111 1800 428 111 Australia 1855 ICT 9111 1855 428 9111 USA Canada Email sales ict co or support ict co mailto support ict co Web www ict co ...

Страница 34: ...94 Designers manufacturers of integrated electronic access control security and automation products Designed manufactured by Integrated Control Technology Ltd Copyright Integrated Control Technology Limited 2003 2017 All rights reserved Disclaimer Whilst every effort has been made to ensure accuracy in the representation of these products neither Integrated Control Technology Ltd nor its employees...

Отзывы: